Call switch with 2 connection sockets, order no. 19 0704 20<br />

Connection on terminal, order no. 19 0700 x0, or display module, order no. 19 0700 80, or RAB,<br />

order no. 19 0701 00 (CONCENTO PLUS system)<br />

GND<br />

Reassurance light<br />

See table below<br />

Call input<br />

+24 V<br />

Order no. 19 0700 x0<br />

or 19 0700 80<br />

or 19 0701 00<br />

Device Order no.<br />

Display module 19 0700 80<br />

RAB<br />

19 0701 00<br />

Terminal 19 0700 x0<br />

BK<br />

YE<br />

WH(YE)<br />

RD<br />

IY(ST)Y 2x2x0.8 mm<br />

Call type Reassurance light Call input<br />

1 )<br />

WC Call WL WR<br />

Call Bed 1 RL R1<br />

Call Bed 2 RL<br />

R2<br />

Call Bed 3 RL R3<br />

WC Call WL R3<br />

Call Bed 1 RL R1<br />

Call Bed 2 RL<br />

R2<br />

1 ) Note! Many inputs of the display module, RAB and terminals are configurable, i.e<br />

the call type can be changed. In addition there are further inputs available that are also<br />

configurable. For details, read the product leaflet accompanying the respective device.<br />

Several call buttons in the room<br />

Max. 4 call devices can be connected in line or star topology. The max. cable length per input is 20 m. The integrated 120 kOhm<br />

terminating resistor must be active for all call devices (= factory setting).<br />

Light switching<br />

same as LT1, but for pear push switch 2<br />

24 V DC not from<br />

the nurse call system<br />

Light<br />

230 V AC<br />

Light switching - see below<br />

IY(ST)Y 2x2x0.8 mm<br />

Pulse relay<br />

LT2<br />

LT2<br />

LT1<br />

LT1<br />

GND<br />

RL<br />

RT<br />

+24 V<br />

Connector 7<br />

on switch<br />

00 8814 11, 10/12 (Rev. 2.0) 2<br />

<strong>Technical</strong> <strong>Manual</strong> Page 120<br />

RD<br />

BK<br />

WH(YE)<br />

YE<br />

Caution! Do not change the DIP switch or jumper 6. It must be in the ”RA ON” position.<br />

Recommended pulse relays:<br />

Anti-surge diode<br />

min. 1N4007<br />

Pulse relay (electronic): Pulse relay (mechanical*): Switching relay (mechanical) *):<br />

ELTAKO, ES60-TX60-24VDC<br />

ELTAKO, ES75-100-12..24 VDC<br />

SCHIELE entrelec TX60-24V<br />

BIAIG electronics TX60-24V<br />

ELTAKO, 1S9-24 VDC<br />

ELTAKO, S91-100-24 VDC<br />

LT2<br />

LT2<br />

LT1<br />

LT1<br />

GND<br />

RL<br />

RT<br />

+24 V<br />

Connector 7 on switch<br />

same as LT1, but pear push switch 2<br />

Light button on pear push switch 1<br />

Pear push switch 1<br />

Pear push switch 2<br />

ELTAKO, R12-100-24 VDC (for DIN rail)<br />

ELTAKO, R91-100-24 VDC (Flush-mounted, surface-mounted version)<br />

FINDER, 49.61-7024.4050<br />