Power supply unit UPS, Order No. 77 3400 00<br />

2.3.1 Preparing the UPS function by placing a bridge contact between "x" and "y"<br />

• Connect the control terminal clamps "x" and "y" using the enclosed bridging contact or via a<br />

potential-free 'make contact'. The current for the bridging contact is approx. 1 mA..<br />

2.3.2 LED and indicator outputs 1 - 5<br />

The five indicator outputs 1 – 5 at the 7-pole terminal block indicate the status of the unit via potentialfree<br />

solenoid contacts. The current load for these contacts is up to 125 V / 1.5 A / 60 VA.<br />

2.3.2.1 Green LED "Power" (mains supply mode and bridging contact between "x" and "y"<br />

closed)<br />

Only green LED "Power“ is on.<br />

Contacts 3 – 1 & 3 - 5 are closed.<br />

2.3.2.2 Amber LED "Battery active"<br />

Only amber LED "Battery active“ is on.<br />

Contacts 3 – 1 & 3 – 4 are closed.<br />

2.3.2.3 Red LED "Battery low"<br />

During mains failure<br />

Only amber LED "Battery active“ is on.<br />

Contacts 3 – 1 & 3 – 4 are closed.<br />

Amber LED "Battery active“ and red LED "Battery<br />

low“ are on.<br />

Contacts 3 – 2 & 3 – 4 are closed.<br />

All LEDs are off.<br />

Contacts 3 – 2 & 3 – 5 are closed.<br />

24 V voltage is available at the terminal clamp.<br />

Battery mode<br />

(when bridging contact between "x" and "y" is<br />

closed)<br />

The 24 V voltage at the terminal clamp is from the<br />

battery.<br />

The voltage at the terminal clamps depends on<br />

the relevant battery charge state.<br />

When the output voltage has dropped to<br />

approx. 19.5 V, the power supply unit will shut off<br />

(protection against totally flat battery)<br />

After the input voltage (115 - 230 Volt) has been reactivated again, the output clamps will be supplied<br />

with 24 V DC, and the batteries will be recharged automatically.<br />

2.3.2.4 Red LED "Output Failure Fuse F2" defective<br />

Green LED "Power“ and red LED "Output Failure<br />

Fuse F2" are on<br />

2.3.4 Battery test<br />

Green LED "Power“ is on and red LED "Battery<br />

low“ illuminates for 30 seconds every 15 minutes.<br />

Contact 3 – 2 is closed for 30 seconds every 15<br />

minutes.<br />

Output fuse F2 was removed or it is defective. No<br />

output voltage at the power supply terminal<br />

clamps.<br />

Battery capacity not sufficient for safe UPS<br />

operation.<br />

Batteries are automatically checked every 15<br />

minutes. If a battery fault is detected during this<br />

test, the indicating contact and the LED "Battery<br />

low" are activated for the approx. 30 sec. test<br />

period.<br />

The unit features an automatic battery load test. For this, the internal batteries' status is checked at<br />

regular intervals (approx. 15 minutes).<br />

This takes place by voltage measuring while simultaneously demanding a defined load current for a<br />

period of approx. 30 sec.<br />