7. Defining mounting positions<br />

7.2 Mounting heights<br />

50<br />

Specified mounting heights in accordance with the German standard DIN VDE<br />

0834-1:2000:<br />

Mounting height above the floor:<br />

Devices for operation (with and without indicator lamps) 700 - 1,500 mm<br />

Devices for operation with text displays 1500 - 1,700 mm<br />

Devices in installation units 1600 - 1,800 mm<br />

Signal lamps and large-text displays 1500 - 2,200 mm<br />

Distribution boxes 700 - 2,200 mm<br />

Pull cord switches or similar in shower cubicles 200 mm above the<br />

highest possible<br />

shower head posi‐<br />

tion<br />

CONCENTO PLUS - <strong>Technical</strong> <strong>Manual</strong>, 11/12 (Rev. 3.0), 00 8814 14