3. Commissioning<br />

Power supply unit, Order No. 77 3401 00<br />

1. Connect input and output terminal connections. (Refer to items 2.1 and 2.2)<br />

2. Switch on the input voltage.<br />

From now on, the connected nurse call system devices are supplied with 24 V DC.<br />

The green LED "Power" is on due to the voltage at the terminal clamps.<br />

4. Spare parts<br />

Spare part Order No.<br />

Mains Fuse F1 (5 x 20) T 5,0 A 00 0130 41<br />

Output fuse F2 FKS 15 A 00 0132 02<br />

Clamp for input voltage, 3-pole 00 0211 40<br />

Clamp for 0 V and +24 V, 4-pole 00 0211 41<br />

Indicator clamp, 7-pole 00 0211 39<br />

5. <strong>Technical</strong> data<br />

Power supply unit<br />

Input<br />

Order No. 77 3401 00<br />

Nominal input voltage 115 – 230 V AC<br />

Input voltage range 90 – 264 V AC<br />

Input frequency 47 – 63 Hz<br />

Input current 4 A at 115 V AC / 2 A at 230 V AC<br />

Start-up current surge 22 A at 115 V AC / 44 A at 230 V AC, typical<br />

Power factor 0.95 at 230 V AC / 0.98 at 115 V AC under full load<br />

Efficiency<br />

Output<br />

88%, typical<br />

Nominal output current 12,5 A DC<br />

Output voltage 24 V DC +/- 2%<br />

Calculated output power 288 W<br />

Rippling of nominal output current < 100 mVeff<br />

Overload protection, power supply unit,<br />

internal<br />

< 14 A<br />

Overvoltage protection, power supply<br />

unit<br />

26.7 – 32.4 V DC, typical<br />

Overtemperature protection 75 °C +/- 5°C (power diode)<br />

output voltage switched off, automatic re-engaging<br />

EMC CE-certified EN 55022 Class B; ENV 50204<br />

EN 61000-3-2, -3; EN 61000-4-2, -3, -4, -5, -6, -8, -11<br />

Safety EN 60950<br />

Output Safety low voltage SELV<br />

Test voltage PRI – SEC 3 kV<br />

Protection class Class I<br />

Protection<br />

Safety devices<br />

IP 20<br />

Mains Fuse F1 (5 x 20) T 5.0 A<br />

Output fuse F2 FKS<br />

General<br />

15 A FKS<br />

Cooling Convection, free airflow<br />

Permissible ambient temperature 0 ... +50 °C<br />

Storage temperature -25 ... + 60 °C<br />

MTBF 100,000 hours<br />

Weight approx. 2 kg<br />

Dimensions (HxWxD) 244 x 325 x 178 mm<br />

Mounting Wall mounting<br />

Connecting clamps Screw / plug-in clamps<br />

© <strong>Tunstall</strong> <strong>GmbH</strong>, Orkotten 66, 48291 Telgte, Germany, www.tunstall.de, 00 8802 42, Rev. 3.1 (05/2008) English - 3<br />