7.3.3 Switches<br />

ÀÀ<br />

ÀÀÀÀÀ<br />

ÀÀÀ<br />

150 mm<br />

300 mm<br />

1,300 mm<br />

1,000 mm<br />

CONCENTO PLUS - <strong>Technical</strong> <strong>Manual</strong>, 11/12 (Rev. 3.0), 00 8814 14<br />

7. Defining mounting positions<br />

Cancel switch next to the door in the WC<br />

Order no.: 19 0708 50, 19 0709 00<br />

A 1-gang back box is required for each switch. .<br />

Call switch<br />

Order no.: 19 0708 00<br />

A 1-gang back box is required for each switch.<br />

The call switch must be easily reachable, e.g. next to the<br />

washbasin.<br />

300 mm Pull cord switch in the bathroom/WC<br />

(ceiling mounting)<br />

300 mm<br />

2,250 mm<br />

Order no.: 19 0707 20x<br />

1-gang back box required.<br />

The special requirements for ”barrier-free living” (DIN 18025)<br />

must be observed in the case of pull cord switches in wet<br />

rooms. Here too, persons lying on the floor must be able to<br />

reach the pull cords. This means that the call handle must not<br />

be more than 200 mm above the floor.<br />

Pull cord switch in the bathroom/WC<br />

(wall mounting)<br />

Order no.: 19 0707 20x<br />

1-gang back box required.<br />

Pull cord switches in wet rooms must be installed at least 200<br />

mm above the highest possible shower head position.<br />

The special requirements for ”barrier-free living” (DIN 18025)<br />

must be observed in the case of pull cord switches in wet<br />

rooms. Here too, persons lying on the floor must be able to<br />

reach the pull cords. This means that the call handle must not<br />

be more than 200 mm above the floor.<br />

53