7. Defining mounting positions<br />

7.1 General requirements<br />

All devices of the nurse call<br />

system<br />

CONCENTO PLUS - <strong>Technical</strong> <strong>Manual</strong>, 11/12 (Rev. 3.0), 00 8814 14<br />

- Unambiguous call raising and simple handling must be ensu‐<br />

red for the changing users, and the possibility of mix-ups with<br />

parts of other systems must be eliminated.<br />

- Damage or destruction by external influences that can be ex‐<br />

pected during proper use (e.g. bed transport) must be impossi‐<br />

ble.<br />

- May not be installed in rooms that can have harmful effects on<br />

telecommunications systems.<br />

Devices with displays - Must be well within the field of vision (terminals, display mo‐<br />

dule).<br />

- Should not be subjected to direct sunlight<br />

Call switches, call devices - Must be in easy reach.<br />

Presence buttons - Near doors<br />

Visual signalling devices - Recognition must not be impaired by light from other sources.<br />

Signal lamps, corridor displays - Must guide the called or sought persons to the call location via<br />

the shortest route.<br />

Room lamps - Must be easily assignable to the rooms.<br />

In WCs and wet rooms - Observe the special regulations of DIN VDE 0100!<br />

Power supply units, Group<br />

Electronics, Management<br />

Interface, fire alarm interface<br />

Distribution boxes that are<br />

used jointly for the nurse call<br />

system and power system<br />

- Only in dry rooms, ideally in a distribution box (not in pati‐<br />

ents'/residents' rooms).<br />

- Easily accessible at all times (access space min. 60 cm width).<br />

- Heat dissipation must not be obstructed.<br />

- In the case of installation in switch cabinets etc., the heat loss<br />

must be dissipated by forced ventilation if necessary.<br />

- Due to the voltage drop, the power supply unit should, if possi‐<br />

ble, be housed close to the largest consumers.<br />

- Fire hazard! Heat is produced in short-circuit operation of<br />

power supply units. Make sure thatt here is sufficient ventilation<br />

in the distribution box.<br />

- After the outer cover is removed, the power section must re‐<br />

main covered.<br />

- The terminals for the nurse call system and the power system<br />

must differ from each other clearly, e.g. in shape and/or colour.<br />

Labelling alone is not a sufficient distinguishing feature.<br />

- Spatially separate arrangement.<br />