8. Laying cables<br />

8.6 Secondary lines (code: a)<br />

Ward bus<br />

66<br />

19 0700 20<br />

The cable system with room devices that is connected to a defined input of a<br />

room terminal is designated as a secondary line. Room terminals are Terminal<br />

SD6 P, Terminal S4 P, Terminal S4 B, the display module and the call/presence<br />

combination bus (RAB). The number of secondary lines, i.e. the number of in‐<br />

puts of a room terminal, depends on the devices and can be found in the room<br />

terminal's product leaflets.<br />

Room devices that are connected to the secondary lines are:<br />

Room lamp<br />

All switches<br />

Call switch with connection socket<br />

Call switch with 2 connection sockets<br />

Sensor mat with free cable ends<br />

Smoke detector<br />

The cable type for secondary lines is ”a”, i.e. a standard telecommunications<br />

cable IY(ST)Y 2x2x0.8 mm.<br />

Note! Switches with 2 buttons, e.g. the call & cancel switch/WC, order<br />

no.19 0708 50, are connected differently to all other room devices with the ca‐<br />

ble type ”c”, i.e. a standard telecommunications cable IY(ST)Y 4x2x0.8 mm.<br />

Each room device (apart from the room lamp) must be terminated with a<br />

120 kOhm resistor. Even when several room devices are connected to one<br />

defined secondary line, each of these devices must be terminated with a<br />

120 kOhm resistor. The resistor is already present in the devices. Refer to the<br />

product leaflet for the respective device for details of how to activate the termin‐<br />

ating resistor.<br />

Note! The maximum permissible cable length of each secondary line is 20 m<br />

in total. A maximum of 4 room devices may be connected to one defined secon‐<br />

dary line, i.e. at one input of a room terminal.<br />

a<br />

Secondary line<br />

Secondary line<br />

Secondary line<br />

Secondary line<br />

a<br />

77 0180 10<br />

4x2x0.8<br />

a<br />

19 0708 50<br />

19 0704 00 19 0704 00<br />

a a<br />

19 0708 00<br />

a<br />

19 0704 00<br />

19 0707 20x<br />

19 0704 00<br />

CONCENTO PLUS - <strong>Technical</strong> <strong>Manual</strong>, 11/12 (Rev. 3.0), 00 8814 14