AC<strong>iC</strong> Operator’s <strong>Manual</strong> Revision 4 Page 25 of 95<br />

ENABLE EARLY ARR: This enables a special arrival window that occurs prior to the Fast Arrival<br />

Window. When an Early Arrival occurs, both Current Early and Current Fast counters are<br />

reduced and Fast Adjustments are made.<br />

27 EARLY TIME: This time setting creates the Early Window. From the start of the On Time to the<br />

Early Time value is the Early Window. A plunger arrival time less than the Early Time would be<br />

in the Early Window.<br />

28 INITIAL EARLY: This counter is the initial setting for the Early Window. It determines how many<br />

consecutive Early Arrivals the well can make before shut-in occurs. The value will not change<br />

unless you modify the default setting.<br />

29 CURRENT EARLY: This counter is the Current or Present count of plunger arrivals in the Early<br />

Window. The Current Early Counter is reduced each time the plunger arrives in the Early<br />

Window. Once the present counter reaches 0 the well will be shut-in. Any Fast or Good Arrival<br />

will automatically reset this counter to the Initial No Arrival value.<br />

30 TANK DELAY: This is the delay time before the second motor valve is allowed to open. Tank Delay<br />

Time always starts timing at the beginning of the Tubing On Time. It is generally used to sell<br />

higher-pressure gas down the gas sales line before having to open to a lower pressure in order<br />

to surface the plunger. If the plunger arrives before the delay time expires the Tank On Time is<br />

bypassed. This option is only available if the Tank Control Mode is selected.<br />

31 TANK ON: This is the total time the tank valve will be open (provided that the plunger has not<br />

arrived). The Tank On Time starts at the end of the Tank Delay Time. If the tank valve opens<br />

and the plunger arrives during the Tank On Time, the tank valve will close and the Tubing valve<br />

will either start the Afterflow cycle or shut-in (depending on the program status). This option is<br />

only available if the Tank Control Mode is selected.<br />

102 RECVRY OFFT: This is a special Off Time used during LL3 recovery mode. The Recovery Off Time<br />

will run instead of the Off Time after the initial counts have been satisfied.<br />

121 INIT RECVRY CNT: This counter is the initial setting for the LL3 Recovery Mode. It determines how<br />

many consecutive no arrivals the well can make before using the Recovery Off Time. The value<br />

will not change unless you modify the default setting.<br />