AC<strong>iC</strong> Operator’s <strong>Manual</strong> Revision 4 Page 77 of 95<br />
Use ROCLINK 800 to connect to the ROC 809.<br />
From the ROC menu, select Comm Ports.<br />
Choose the Comm port being used from the menu.<br />
Set the Baud Rate, Data Bits, Parity, and Stop Bits to<br />
19200, 8, None, and 1.<br />
Set the Port Owner to Modbus Slave Only.<br />
Click Apply. Click OK.<br />
Figure 7.23: ROC Modbus Configuration<br />
Figure 7.22: ROC Communications Configuration<br />
7. From the Configure menu, choose Modbus, then<br />
Configuration.<br />
8. Choose the Comm port being used from the menu.<br />
9. Set the Byte Order to Most Significant Byte First.<br />
10. Click Apply. Click OK.<br />