From the Configure menu, choose Modbus and then Registers.<br />

Enter the information in to Table 7.16 or Table 7.17. Be sure to choose the proper Turbine or Orifice Meter if there<br />

is more than one being controlled by the device. The AC<strong>iC</strong> can utilize only one flow measurement device.<br />

Assign the entered registers to the Comm port being used. Click Apply. Click Update.<br />

Starting Register Ending Register Point Type Parameter Indexing Conversion<br />

7001 7001 115 16 Parameter 0<br />

7002 7002 115 18 Parameter 0<br />

7003 7003 116 0 Parameter 0<br />

7004 7005 116 12 Parameter 0<br />

Table 7.16: ROC 800 Turbine Meter Configuration<br />

Starting Register Ending Register Point Type Parameter Indexing Conversion<br />

7000 7000 113 26 Parameter 0<br />

7001 7001 113 28 Parameter 0<br />

7002 7002 113 30 Parameter 0<br />

7003 7003 114 0 Parameter 0<br />

7004 7005 114 19 Parameter 0<br />

Table 7.17: ROC 800 Orifice Meter Configuration<br />

Figure 7.24: ROC Parameter Assignment<br />

Figure 7.25: ROC Modbus Register Assignment<br />