From the Configure menu, choose Modbus and then Registers.<br />
Enter the information in to Table 7.16 or Table 7.17. Be sure to choose the proper Turbine or Orifice Meter if there<br />
is more than one being controlled by the device. The AC<strong>iC</strong> can utilize only one flow measurement device.<br />
Assign the entered registers to the Comm port being used. Click Apply. Click Update.<br />
Starting Register Ending Register Point Type Parameter Indexing Conversion<br />
7001 7001 115 16 Parameter 0<br />
7002 7002 115 18 Parameter 0<br />
7003 7003 116 0 Parameter 0<br />
7004 7005 116 12 Parameter 0<br />
Table 7.16: ROC 800 Turbine Meter Configuration<br />
Starting Register Ending Register Point Type Parameter Indexing Conversion<br />
7000 7000 113 26 Parameter 0<br />
7001 7001 113 28 Parameter 0<br />
7002 7002 113 30 Parameter 0<br />
7003 7003 114 0 Parameter 0<br />
7004 7005 114 19 Parameter 0<br />
Table 7.17: ROC 800 Orifice Meter Configuration<br />
Figure 7.24: ROC Parameter Assignment<br />
Figure 7.25: ROC Modbus Register Assignment<br />