10. Click on the Measurement tree and select the Current Values tab.<br />

11. Ensure the numerical identifier corresponds with Table 7.22. If not, write down the numerical identifiers for each<br />

item.<br />

12. From the Operate menu, select File Utilities and select Save and Restore Utility<br />

13. Expand the R: Tree and select Modbus.<br />

14. From the Operate menu, select File Utilities and select Modbus Slave Register Editor.<br />

15. Enter 7001 for Map Start and 6 for # Registers. Select Register List from the View menu.<br />

16. Using Table 7.22, fill in the register numbers.<br />

17. Select Send and enter an appropriate file name of your choice.<br />

18.<br />

19.<br />

20.<br />

Totalflow<br />

Register<br />

Description<br />

Modbus<br />

Register<br />

11.3.0 Static Pressure 7001<br />

11.7.0 Differential Pressure 7002<br />

11.3.3 Temperature 7003<br />

11.7.19 Flow Rate 7004<br />

11.7.22 Today’s Volume 7005<br />

11.7.23 Yesterday’s Volume 7006<br />

Table 7.22: Totalflow Modbus Register Map<br />

Press the Save Station Files button and select an appropriate file directory.<br />

Once the save is completed, answer Yes to restoring files to the S: drive.<br />

Click OK to complete the restore.<br />

Figure 7.32: Totalflow Save Station Files<br />

Figure 7.31: Totalflow Register Map<br />

2913 Specialty Drive • P.O. Box 130158 • Tyler, TX 75713-0158 • Phone: 903-561-4851 • Fax: 903-561-6567