AC<strong>iC</strong> Operator’s <strong>Manual</strong> Revision 4 Page 34 of 95<br />

4.7.5 F5 <strong>–</strong> Overrides<br />

70 OPN IF CP >=: Open the Tubing Valve if the Casing Pressure is equal-to or greater-than the PSIG<br />

setting and the Minimum Off Time has expired.<br />

71 OPN IF TP >=: Open the Tubing Valve if the Tubing Pressure is equal-to or greater-than the PSIG<br />

setting. And the Minimum Off Time has expired.<br />

100 OPN IF TP-LP >: Open the Tubing Valve if the Tubing Pressure <strong>–</strong> Line Pressure is greater than the<br />

PSIG setting and the Minimum Off Time has expired.<br />

OPN IF TP-RMLP >: Open the Tubing Valve if the Tubing Pressure <strong>–</strong> Remote Line Pressure is<br />

greater than the PSIG setting and the Minimum Off Time has expired.<br />

101 OPN IF FSLUG >=: Open the Tubing Valve if the Fluid Slug setting is equal-to or greater-than the<br />

PSIG setting and the Minimum Off Time has expired.<br />