AC<strong>iC</strong> Operator’s <strong>Manual</strong> Revision 4 Page 68 of 95<br />
Use ROCLINK 800 to connect to the FloBoss 103/503.<br />
From the ROC menu, select Comm Ports.<br />
Choose the Comm port being used from the menu.<br />
Use the configuration from Figure 7.7.<br />
Click Apply. Click OK.<br />
Figure 7.7: FloBoss 103/503 Communications<br />
! Ensure no user programs, including but not limited to Modbus Host, are<br />
currently using the COM Port intended to be used as the Modbus Slave.<br />
From the Configure menu, choose Modbus, then Configuration.<br />
Choose Most Significant Byte First.<br />
Click Apply. Click OK.<br />
Figure 7.6: Modbus Host Program<br />
Figure 7.8: FloBoss 103/503 Modbus Configuration<br />