AC<strong>iC</strong> Operator’s <strong>Manual</strong> Revision 4 Page 88 of 95<br />

7.5.1 AC<strong>iC</strong> Configuration for AutoPILOT<br />

1. Open the AC<strong>iC</strong> in <strong>iC</strong>Connect and choose the Input Config tab<br />

2. Set the Differential pressure analog channel, Line Pressure analog channel, and Line Temperature analog<br />

channel to FCU.<br />

3. Click the Save button.<br />

4. Choose System tab.<br />

5. Set the port setup sections according to Table 7.26.<br />

6. Click the Save button.<br />

7. Choose the FCU tab.<br />

8. Set the appropriate MODBUS address of the AutoPILOT.<br />

9. Set all the other FCU parameters as according to Table 7.27.<br />

10. Click the Save button.<br />

Setting Value<br />

Port Setup (Serial or TTL)<br />

Baud Rate 19200<br />

Parity None<br />

Flow Control No flow control<br />

Stop Bits 1 Stop bit<br />

Data Bits 8 Data bits<br />

Port Device External Device<br />

Port Protocol Flow computer (FCU)<br />

Table 7.26: <strong>iC</strong>Connect System Tab - AutoPILOT<br />

Setting Value<br />

Capture window<br />

Previous volume capture window end 60<br />

Previous volume capture window start 0<br />

FCU Communications<br />

FCU’s MODBUS mode False<br />

FCU’s slave mode True<br />

Flow computer present True<br />

MODBUS address 1<br />

Prefix byte 0<br />

Prefix byte count 0<br />

Suffix byte 0<br />

Suffix byte count 0<br />

FCU Data Format<br />

Byte order DCBA<br />

Data type Single precision float<br />

Flow computer type Fisher ROC<br />

Flow rate definition MCF per day<br />

Units False<br />

FCU Registers<br />

Current volume address 7905<br />

DP address 7901<br />

Flow address 7904<br />

LT address 7903<br />

Previous volume address 7906<br />

SP address 7902<br />

Totalflow base group number 0<br />

FCU Scan<br />

Response timeout 7<br />

Scan interval 1<br />

Table 7.27: <strong>iC</strong>Connect FCU Tab - AutoPILOT<br />