AC<strong>iC</strong> Operator’s <strong>Manual</strong> Revision 4 Page 88 of 95<br />
7.5.1 AC<strong>iC</strong> Configuration for AutoPILOT<br />
1. Open the AC<strong>iC</strong> in <strong>iC</strong>Connect and choose the Input Config tab<br />
2. Set the Differential pressure analog channel, Line Pressure analog channel, and Line Temperature analog<br />
channel to FCU.<br />
3. Click the Save button.<br />
4. Choose System tab.<br />
5. Set the port setup sections according to Table 7.26.<br />
6. Click the Save button.<br />
7. Choose the FCU tab.<br />
8. Set the appropriate MODBUS address of the AutoPILOT.<br />
9. Set all the other FCU parameters as according to Table 7.27.<br />
10. Click the Save button.<br />
Setting Value<br />
Port Setup (Serial or TTL)<br />
Baud Rate 19200<br />
Parity None<br />
Flow Control No flow control<br />
Stop Bits 1 Stop bit<br />
Data Bits 8 Data bits<br />
Port Device External Device<br />
Port Protocol Flow computer (FCU)<br />
Table 7.26: <strong>iC</strong>Connect System Tab - AutoPILOT<br />
Setting Value<br />
Capture window<br />
Previous volume capture window end 60<br />
Previous volume capture window start 0<br />
FCU Communications<br />
FCU’s MODBUS mode False<br />
FCU’s slave mode True<br />
Flow computer present True<br />
MODBUS address 1<br />
Prefix byte 0<br />
Prefix byte count 0<br />
Suffix byte 0<br />
Suffix byte count 0<br />
FCU Data Format<br />
Byte order DCBA<br />
Data type Single precision float<br />
Flow computer type Fisher ROC<br />
Flow rate definition MCF per day<br />
Units False<br />
FCU Registers<br />
Current volume address 7905<br />
DP address 7901<br />
Flow address 7904<br />
LT address 7903<br />
Previous volume address 7906<br />
SP address 7902<br />
Totalflow base group number 0<br />
FCU Scan<br />
Response timeout 7<br />
Scan interval 1<br />
Table 7.27: <strong>iC</strong>Connect FCU Tab - AutoPILOT<br />