From the Run/Function Configuration tree, select RTU Port Configuration.<br />

Using the AC<strong>iC</strong> Modbus Register Map, configure up to 14 32-bit Floating Point (Daniel Float) values or 16-bit<br />

Integer (Word Value) values. Use the Modbus address of the AC<strong>iC</strong> and scale of 1 to read directly. Other scaling<br />

may be applied as necessary.<br />

Figure 8.6: AutoPILOT Scanner Register Configuration<br />

Registers in the AC<strong>iC</strong> are numbered at Base 1 and register numbers in the<br />

AutoPILOT are Base 0. To simplify this, subtract 1 from register numbers as<br />

shown in the AC<strong>iC</strong> Modbus register map before entering them into AUTOConifg.<br />

! The AutoPILOT only supports 32-bit Floating Point and 16-bit Integer registers.<br />

No other register types are supported.<br />