AC<strong>iC</strong> Operator’s <strong>Manual</strong> Revision 4 Page 89 of 95<br />

7.5.2 AutoPILOT Configuration<br />

1. Connect to the AutoPILOT using the AutoCONFIG software.<br />

2. From the System Configurations tree, select System<br />

Configuration.<br />

3. Set the Host Baud Rate to 19200 Comm. Address to the<br />

MODBUS Address value assigned in the AC<strong>iC</strong>.<br />

4. Click Apply.<br />

5. From the System Configurations tree, select Configurable<br />

Modbus Registers.<br />

6.<br />

7.<br />

For orifice 1, enter values as shown in Table 7.28.<br />

Click Download.<br />

For other orifices, add 100 per orifice number (i.e. 8101 for<br />

orifice 2, 8201 for orifice 3, etc.)<br />

Figure 7.39: System Configuration<br />

Register<br />

Number<br />

Data<br />

7901 8001<br />

7902 8002<br />

7903 8003<br />

7904 8004<br />

7905 8005<br />

7906 8008<br />

Table 7.28: Configurable<br />

Modbus Registers<br />

2913 Specialty Drive • P.O. Box 130158 • Tyler, TX 75713-0158 • Phone: 903-561-4851 • Fax: 903-561-6567