AC<strong>iC</strong> Operator’s <strong>Manual</strong> Revision 4 Page 89 of 95<br />
7.5.2 AutoPILOT Configuration<br />
1. Connect to the AutoPILOT using the AutoCONFIG software.<br />
2. From the System Configurations tree, select System<br />
Configuration.<br />
3. Set the Host Baud Rate to 19200 Comm. Address to the<br />
MODBUS Address value assigned in the AC<strong>iC</strong>.<br />
4. Click Apply.<br />
5. From the System Configurations tree, select Configurable<br />
Modbus Registers.<br />
6.<br />
7.<br />
For orifice 1, enter values as shown in Table 7.28.<br />
Click Download.<br />
For other orifices, add 100 per orifice number (i.e. 8101 for<br />
orifice 2, 8201 for orifice 3, etc.)<br />
Figure 7.39: System Configuration<br />
Register<br />
Number<br />
Data<br />
7901 8001<br />
7902 8002<br />
7903 8003<br />
7904 8004<br />
7905 8005<br />
7906 8008<br />
Table 7.28: Configurable<br />
Modbus Registers<br />