Appendix 129/132<br />
Value<br />
Meaning<br />
GIF/SIF 0x00 00 free place<br />
GIF 0x01 – 0x0E 01 – 14 free place and 1-14 manufacturer specific data<br />
GIF 0x0F 15 free place and no manufacturer specific data<br />
GIF 0x40 64 1 length byte Input<br />
GIF 0x41 – 0x4E 65 – 78 1 length byte Input and 1-14 manufacturer specific data<br />
GIF 0x4F 79 1 length byte Input and no manufacturer specific data<br />
GIF 0x80 128 1 length byte Output<br />
GIF 0x81 – 0x8E 129 – 142 1 length byte Output 1 and 1-14 manufacturer specific data<br />
GIF 0x8F 143 1 length byte Output 1 and no manufacturer specific data<br />
GIF 0xC0 192 1 length byte Output and 1 length byte Input<br />
GIF 0xC1 –<br />
0xCE<br />
193 – 206 1 length byte Output, 1 length Input byte and 1-14<br />
manufacturer specific data<br />
GIF 0xCF 207 1 length byte Output, 1 length Input byte and no manufacturer<br />
specific data<br />
Table 64: Special Identifier bytes 0x01 .. 0x0F, 0x40 .. 0x4F, 0x80 .. 0x8F, 0xC0 .. 0xCF<br />
(SIF)<br />
Length Byte<br />
Value<br />
Meaning<br />
0x00 – 0x3F 00-63 1-64 Byte Consistency over Byte<br />
0x40 – 0x7F 64-127 1-64 Word Consistency over Word<br />
0x80 – 0xBF 129-191 1-64 Byte Consistency over whole length<br />
0xC0 – 0xFF 193-255 1-64 Word Consistency over whole length<br />
Table 65: Length byte of the special identifiers (SIF)<br />