Configuration 66/132<br />
4.9.1 Start of Bus Communication<br />
Figure 39: Device Settings > Start of Bus Communication<br />
4.9.2 Application Monitoring<br />
If Automatically by device is selected, the <strong>PROFIBUS</strong> <strong>DP</strong> Master device<br />
starts with the data exchange on the bus after the initializing has been<br />
ended.<br />
When Controlled by application is selected, the application program must<br />
activate the data exchange on the bus.<br />
Note: The setting options under Start of Bus Communication for client<br />
specific variants of the configuration software can differ from the setting<br />
options displayed here.<br />
Figure 40: Device Settings > Application Monitoring<br />
The Watchdog time determines the time within which the device watchdog<br />
must be re-triggered from the application program while the application<br />
program monitoring is activated. When the watchdog time value is equal to<br />
0 the watchdog is deactivated and the application program monitoring is<br />
deactivated too.<br />
The permissible range of values of the watchdog time is 20 to 65535. By<br />
default the watchdog time value equals to 1000 ms.<br />
Watchdog time<br />
Permissible range of values<br />
Default<br />
The software watchdog is deactivated.<br />
Table 21: Range of Value / Value for the Watchdog time<br />
Range of Value / Value<br />
20 … 65535 ms<br />
1000 ms<br />
0 ms<br />
Note: The setting options under Application Monitoring for client<br />
specific variants of the configuration software can differ from the setting<br />
options displayed here.<br />
<strong>DTM</strong> for Hilscher <strong>PROFIBUS</strong> <strong>DP</strong> <strong>Slave</strong> Device | Configuration of Hilscher <strong>Slave</strong> Devices<br />
DOC091001OI07EN | Revision 7 | English | 2011-09 | Released | Public © Hilscher, 2009-2011