Configuration 66/132<br />

4.9.1 Start of Bus Communication<br />

Figure 39: Device Settings > Start of Bus Communication<br />

4.9.2 Application Monitoring<br />

If Automatically by device is selected, the <strong>PROFIBUS</strong> <strong>DP</strong> Master device<br />

starts with the data exchange on the bus after the initializing has been<br />

ended.<br />

When Controlled by application is selected, the application program must<br />

activate the data exchange on the bus.<br />

Note: The setting options under Start of Bus Communication for client<br />

specific variants of the configuration software can differ from the setting<br />

options displayed here.<br />

Figure 40: Device Settings > Application Monitoring<br />

The Watchdog time determines the time within which the device watchdog<br />

must be re-triggered from the application program while the application<br />

program monitoring is activated. When the watchdog time value is equal to<br />

0 the watchdog is deactivated and the application program monitoring is<br />

deactivated too.<br />

The permissible range of values of the watchdog time is 20 to 65535. By<br />

default the watchdog time value equals to 1000 ms.<br />

Watchdog time<br />

Permissible range of values<br />

Default<br />

The software watchdog is deactivated.<br />

Table 21: Range of Value / Value for the Watchdog time<br />

Range of Value / Value<br />

20 … 65535 ms<br />

1000 ms<br />

0 ms<br />

Note: The setting options under Application Monitoring for client<br />

specific variants of the configuration software can differ from the setting<br />

options displayed here.<br />

<strong>DTM</strong> for Hilscher <strong>PROFIBUS</strong> <strong>DP</strong> <strong>Slave</strong> Device | Configuration of Hilscher <strong>Slave</strong> Devices<br />

DOC091001OI07EN | Revision 7 | English | 2011-09 | Released | Public © Hilscher, 2009-2011