WARNING: Installation, usage and maintenance of this product<br />

must be in compliance with all Engineered Controls International,<br />

Inc. instructions as well as requirements and provisions of NFPA<br />

#54, NFPA #58, DOT and all applicable federal, state, provincial<br />

and local standards, codes, rules, regulations and laws.<br />

Inspection and maintenance on a periodic basis is essential.<br />

Installation and maintenance should be performed only by qualified<br />

personnel.<br />

Be sure all instructions are read and understood before installation<br />

and operation.<br />

CAUTION: Contact or inhalation of liquid propane, ammonia and<br />

their vapors can cause serious injury or death! NH3 and LP-Gas<br />

must be released outdoors in air currents that will insure dispersion<br />

to prevent exposure to people and livestock. LP-Gas must be kept<br />

far enough from any open flame or other source of ignition to<br />

prevent fire or explosion! LP-Gas is heavier than air and will not<br />

disperse or evaporate rapidly if released in still air.<br />

Foreword<br />

The A3212TL Thermal Latch is designed especially for use with the<br />

A3212A Series Internal Valves. It is designed to provide thermal<br />

protection for the internal valve installation. Responsibility for<br />

proper installation must be met by the installer.<br />

How The Thermal Latch Works<br />

When the valve’s operating lever is moved to the open position, the<br />

latch automatically holds the lever open. If exposed to fire or<br />

extreme heat, the built-in fusible element is designed to melt and<br />

return the operating lever to the closed position. It is designed to<br />

release when temperature reaches 212° F.<br />

A3212TL Thermal Latch<br />

for A3212A Series<br />

Internal Valves<br />

Thermal Latch Installation — Refer to diagram below.<br />

1. Attach latch support to internal valve using the two socket head<br />

cap screws, placing washers between latch support and internal<br />

valve.<br />

2. Insert a shoulder socket head screw through one of the two<br />

holes located on end of latch support and secure with hex nut.<br />

(Try the hole on the end of the bracket first to achieve maximum<br />

opening of the valve.)<br />

3. Attach latch to lever with a shoulder socket head screw taking<br />

care to orient latch as shown in diagram. Place spacer in<br />

between latch and lever, aligning holes. Place shoulder socket<br />

head screw through holes as shown and tighten securely.<br />

4. Insert Adjusting Screw into latch as shown and thread in about<br />

1<br />

/3 of its length.<br />

5. To engage latch: Rotate latch and lever assembly until notch<br />

in latch connects on shoulder socket head cap screw of latch<br />

support.<br />

6. Adjust the Adjusting Screw to assure maximum open position<br />

of valve.<br />

A3212A Series Valve<br />

Adjusting Screw<br />

Pivot Shaft<br />

Washer<br />

Latch Support<br />

Pin<br />

5<br />

/16" Shoulder<br />

Socket Head<br />

Cap Screws<br />

1<br />

/4-28 x 3 /4 Socket Head<br />

Cap Screw<br />

Spacer<br />

Hex Nut<br />

Lever<br />

Latch