BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />
© Siemens AG 2007<br />
Introduction<br />
Center feeder units<br />
Cable entry is possible from 3 sides. The phase sequence can<br />
be changed on site by rotating the busbar pack.<br />
BD2.-...-ME center feeder units (PE left and PE right)<br />
BD2.-...-ME center feeder units (PE rear and PE front)<br />
NSV0_00125<br />
Tap-off units<br />
Tap-off units are available in a number of versions for different<br />
applications.<br />
BD2-AK1 molded plastic-enclosed tap-off units for up to 25 A<br />
with fuses, miniature circuit-breakers and socket outlets<br />
Features:<br />
• Molded-plastic enclosure, color light gray, similar to RAL 7035<br />
• Transparent cover for the protective elements<br />
• During mounting and removing of the tap-off units, a load<br />
switching capacity of AC-22B up to <strong>40</strong>0 V is reached<br />
• An anti-rotation feature prevents incorrect mounting<br />
• Power pick-up through silver-plated lyra-shaped contacts<br />
• Cables can be introduced from three sides<br />
• The tap-off unit must be removed from the trunking before the<br />
unit can be opened and the cables connected<br />
• Built-in strain relief<br />
• The connection cables should be supported separately if<br />
required<br />
NSV0_00127<br />
Sheet steel-enclosed tap-off units BD2-AK2 up to 63 A and<br />
BD2-AK3 up to 125 A with cover-integrated switch-disconnector<br />
Features:<br />
• Hot-galvanized sheet steel and cover with powder-coated finish,<br />
color light gray, RAL 7035.<br />
• The tap-off units can be mounted and removed only with their<br />
cover open.<br />
• Switch-disconnector integrated into the cover, switching<br />
capacity at 63 A AC-22B up to <strong>40</strong>0 V or at 125 A AC-21B,<br />
which ensures that the unit is not live when the cover is open.<br />
• An anti-rotation feature prevents incorrect mounting.<br />
• Cables can be introduced from three sides; use plastic cable<br />
glands with strain relief (not supplied).<br />
• Power pick-up via silver-plated lyra-shaped contacts.<br />
• If the PE conductor is used as a PEN conductor, note that the<br />
PE contact of the BD2-AK3... tap-off units have only half the<br />
cross-section and therefore cannot carry the full rated current.<br />
• The connection cable should be supported separately if<br />
required.<br />
Mounting unit:<br />
For installing devices (e.g. miniature circuit-breakers) in conformance<br />
with DIN 43871, with 8 MW. 1 MW equals a space<br />
requirement of 18 mm. Hinged covers on all tap-off units allow<br />
device operation from outside.<br />
NSV0_00200<br />
BD2-AK2M2/A323<br />
BD2-AK2 tap-off units up to 63 A<br />
with fuses, miniature circuit-breakers and socket outlets<br />
Features:<br />
• Miniature circuit-breakers can optionally be operated from the<br />
outside (mounting unit with 8 MW; 1 MW = 18 mm)<br />
NSV0_00135<br />
5<br />
NSV0_00129<br />
BD2-AK2X/CEE325S33<br />
BD2-AK1/CEE165A163<br />
5/8 Siemens LV 70 · 2006