BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />

© Siemens AG 2007<br />

General data<br />

Trunking units with copper conductor<br />

Type BD2C-.-500 BD2C-.-630 BD2C-.-800 BD2C-.-1000 BD2C-.-1250<br />

Conductors<br />

Rated insulation voltage U i V AC/DC 690/800 690/800 690/800 690/800 690/800<br />

Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3<br />

Rated operational voltage U e V AC 690 690 690 690 690<br />

Frequency Hz 50 ... 60 50 ... 60 50 ... 60 50 ... 60 50 ... 60<br />

Rated current I e = thermal rated current at<br />

A 500 630 800 1000 1250<br />

max. <strong>40</strong> °C and 35 °C on 24 h average<br />

Impedance per unit length of current paths with 50 Hz and<br />

20 °C ambient temperature (cold rails)<br />

•Resistance R 20 mΩ/m 0.113 0.113 0.050 0.050 0.032<br />

• Reactance X 20 mΩ/m 0.053 0.054 0.053 0.053 0.054<br />

• Impedance Z 20 mΩ/m 0.125 0.125 0.073 0.073 0.063<br />

Impedance per unit length of current paths with 50 Hz and<br />

20 °C ambient temperature (rail under operating conditions<br />

warm)<br />

•Resistance R 1 mΩ/m 0.136 0.151 0.065 0.068 0.041<br />

• Reactance X 1 mΩ/m 0.053 0.053 0.053 0.053 0.054<br />

• Impedance Z 1 mΩ/m 0.146 0.<strong>160</strong> 0.084 0.086 0.068<br />

Impedance of conductors under fault conditions<br />

• AC resistance per unit length R F mΩ/m 0.259 0.261 0.136 0.134 0.094<br />

• Reactance per unit length X F mΩ/m 0.218 0.222 0.226 0.227 0.229<br />

• Impedance per unit length Z F mΩ/m 0.338 0.343 0.264 0.264 0.248<br />

Zero impedance according to IEC/EN 60909 Phase to N R 0 mΩ/m 0.532 0.529 0.284 0.284 0.186<br />

(VDE 0102)<br />

X 0 mΩ/m 0.313 0.314 0.261 0.264 0.275<br />

Z 0 mΩ/m 0.617 0.615 0.386 0.388 0.332<br />

Phase to PE R 0 mΩ/m 0.473 0.470 0.258 0.270 0.174<br />

X 0 mΩ/m 0.274 0.277 0.265 0.249 0.265<br />

Z 0 mΩ/m 0.547 0.545 0.370 0.367 0.317<br />

Short-circuit strength<br />

• Rated impulse withstand current I pk kA 59 64 84 90 90<br />

• Rated short-time withstand current I cw t = 1 s kA 21 26 32 34 34<br />

t = 0.1 s kA 28 32 <strong>40</strong> 43 43<br />

Number of conductors 5 5 5 5 5<br />

Conductor cross-section L1, L2, L3 mm 2 158 158 280 418 699<br />

N mm 2 158 158 280 418 699<br />

PE mm 2 158 158 280 418 699<br />

1 / 2 PE mm 2 158 158 158 280 418<br />

5<br />

Conductor material Cu Cu Cu Cu Cu<br />

Max. interval between trunking units<br />

at normal mechanical loading<br />

•Edgewise m 4 4 3.5 3 2<br />

• Edgewise with BD2-BD 1) m 2 2 1.75 1.5 1<br />

•Flat m 3.5 3.5 3 2.5 1.5<br />

Fire load 2) kWh/m 2 2 2 2 2<br />

1) When using BD2-BD spacer bracket.<br />

2) Values for trunking units with tap-off points.<br />

For more values, see page 5/21.<br />