12.03.2015 Views

BD01 System – 40 ... 160 A - GRUP DAP

BD01 System – 40 ... 160 A - GRUP DAP

BD01 System – 40 ... 160 A - GRUP DAP

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />

© Siemens AG 2007<br />

Fire barriers<br />

Fire resistance class S120<br />

• Wall thickness 150 mm ≤ M < 250 mm<br />

(distance from wall/inside corner A ≥ 200 mm)<br />

BD2A-...-L... + BD2-S120-BX*(BY*)-M* 1)<br />

• Junction units LL, LR<br />

M = 150 ... 250 A 200<br />

100 100<br />

NSV0_01029<br />

X*(Y*)(X*(Y*) min. =<br />

285+M+A+170)<br />

BX*(BY*) min. =<br />

285+M/2<br />

810 (min.) 360 360<br />

– – –<br />

1250 (max.) 360 800<br />

• Junction units LV, LH <strong>40</strong>0 A<br />

X*(Y*)(X*(Y*) min. =<br />

285+M+A+70)<br />

BX*(BY*) min. =<br />

285+M/2<br />

710 (min.) 360 360<br />

– – –<br />

1250 (max.) 360 900<br />

• Junction units LV, LH 1000 A<br />

X*(Y*)(X*(Y*) min. =<br />

285+M+A+130)<br />

BX*(BY*) min. =<br />

285+M/2<br />

770 (min.) 360 360<br />

– – –<br />

1250 (max.) 360 8<strong>40</strong><br />

BX*(BY*) max. =<br />

X*(Y*)-170-A-M/2<br />

BX*(BY*) max. =<br />

X*(Y*)-70-A-M/2<br />

BX*(BY*) max. =<br />

X*(Y*)-130-A-M/2<br />

Fire resistance class S120<br />

• Wall thickness M ≥ 250 mm<br />

(distance from wall/inside corner A ≥ 200 mm)<br />

BD2A-...-L... + BD2-S120-BX*(BY*)-M* 1)<br />

• Junction units LL, LR<br />

M 250 A 200<br />

NSV0_01030<br />

X*(Y*)(X*(Y*) min. =<br />

185+M+A+170)<br />

BX*(BY*) min. =<br />

185+M/2<br />

810 (min.) 310 310<br />

– – –<br />

1250 (max.) 310 750<br />

• Junction units LV, LH <strong>40</strong>0 A<br />

X*(Y*)(X*(Y*) min. =<br />

185+M+A+70)<br />

BX*(BY*) min. =<br />

185+M/2<br />

710 (min.) 310 310<br />

– – –<br />

1250 (max.) 310 850<br />

• Junction units LV, LH 1000 A<br />

BX*(BY*) max. =<br />

X*(Y*)-170-A-M/2<br />

BX*(BY*) max. =<br />

X*(Y*)-70-A-M/2<br />

5<br />

1) Replace the asterisk * according to the table.<br />

Note: For other fire barrier configurations, please ask your<br />

contact in your local Siemens branch.<br />

X*(Y*)(X*(Y*) min. =<br />

185+M+A+130)<br />

BX*(BY*) min. =<br />

185+M/2<br />

770 (min.) 310 310<br />

– – –<br />

1250 (max.) 310 790<br />

BX*(BY*) max. =<br />

X*(Y*)-130-A-M/2<br />

5/98 Siemens LV 70 · 2006

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!