© Siemens AG 2007<br />

BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />

Introduction<br />

BD2-AK3 tap-off units up to 125 A<br />

with fuse switch-disconnectors and fuse bases<br />

Features:<br />

• On versions with fuse switch-disconnectors or circuit-breakers,<br />

the cover is interlocked with these switches and can<br />

therefore be opened only when they are switched off.<br />

• On versions with fuse bases, the disconnector built into the<br />

cover does not disconnect the load. It only removes the<br />

voltage from the installed fuse bases when the cover is<br />

opened.<br />

• Terminal bolts for cables.<br />

NSV0_00136<br />

BD2-AK3X/GSTZ00<br />

Tap-off units BD2-AK2 up to 63 A and BD2-AK3 up to 125 A<br />

configured to customer specifications<br />

Features:<br />

• Device installation to customer specification in compliance<br />

with the requirements for type-tested low-voltage switchgear<br />

and controlgear assemblies (TTA). Engineering, quotations<br />

and delivery through your Siemens contacts in our branches.<br />

• Devices mounted on pre-drilled mounting plates, module<br />

mounting rails or top-hat rails according to EN 60715.<br />

BD2-AK02 (AK03) sheet steel-enclosed tap-off units<br />

without cover-integrated switch-disconnector<br />

Features:<br />

• Hot-galvanized sheet steel and cover with powder-coated finish,<br />

color light gray, RAL 7035.<br />

• The tap-off units can be mounted and removed with the cover<br />

open and closed.<br />

• With the cover open the voltage is still applied to the installed<br />

devices (test facility). Degree of protection IP20 (finger-safety)<br />

is assured.<br />

• Do not mount or remove tap-off units under load.<br />

• An anti-rotation feature prevents incorrect mounting.<br />

• Cables can be introduced from three sides; use plastic cable<br />

glands with strain relief (not supplied).<br />

• Power pick-up via silver-plated lyra-shaped contacts.<br />

• If the PE conductor is used as a PEN conductor, note that the<br />

PE contact of the BD2-AK03 tap-off units have only half the<br />

cross-section and therefore cannot carry the full rated current.<br />

• The connection cable should be supported separately if<br />

required.<br />

Mounting unit:<br />

For installing devices (e.g. miniature circuit-breakers) in conformance<br />

with DIN 43871, with 8 MW. 1 MW equals a space<br />

requirement of 18 mm. Hinged covers on all tap-off units allow<br />

device operation from outside.<br />

BD2-AK02 tap-off units up to 63 A<br />

with fuses, miniature circuit-breaker<br />

Features:<br />

• Miniature circuit-breakers can optionally be operated from the<br />

outside (mounting unit with 8 MW; 1 MW = 18 mm)<br />

NSV0_00131<br />

NSV0_00138<br />

BD2-AK2...<br />

BD2-AK02M2/A323<br />

5<br />

Siemens LV 70 · 2006<br />

5/9