BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />

© Siemens AG 2007<br />

Fire barriers<br />

Fire resistance class S120<br />

• Wall thickness M ≥ 150 mm<br />

(distance from wall/inside corner A ≥ 200 mm)<br />

BD2C-...-L... + BD2-S120-BX*(BY*)-M* 1)<br />

• Junction units LL, LR<br />

M 150 A 200<br />

185 185<br />

X*(Y*)(X*(Y*) min. =<br />

370+M+A+170)<br />

BX*(BY*) min. =<br />

370+M/2<br />

890 (min.) 450 450<br />

– – –<br />

1250 (max.) 450 800<br />

• Junction units LV, LH <strong>40</strong>0 A<br />

X*(Y*)(X*(Y*) min. =<br />

370+M+A+70)<br />

BX*(BY*) min. =<br />

370+M/2<br />

790 (min.) 450 450<br />

– – –<br />

1250 (max.) 450 900<br />

BX*(BY*) max. =<br />

X*(Y*)-170-A-M/2<br />

BX*(BY*) max. =<br />

X*(Y*)-70-A-M/2<br />

NSV0_01033<br />

• Junction units LV, LH 1250 A<br />

X*(Y*)(X*(Y*) min. =<br />

370+M+A+130)<br />

BX*(BY*) min. =<br />

370+M/2<br />

850 (min.) 450 450<br />

– – –<br />

1250 (max.) 450 8<strong>40</strong><br />

BX*(BY*) max. =<br />

X*(Y*)-130-A-M/2<br />

Fire resistance class S120<br />

• Wall thickness M ≥ 150 mm<br />

(distance from wall/inside corner 30 mm ≤ A < 200 mm)<br />

BD2C-...-L... + BD2-S120-BX*(BY*)-M* 1)<br />

• Junction units LL, LR<br />

A 30 ... 190<br />

185<br />

X*(Y*)(X*(Y*) min. =<br />

370+M+A+170)<br />

BX*(BY*) min. =<br />

370+M/2<br />

720 (min.) 450 450<br />

– – –<br />

1250 (max.) 450 970<br />

BX*(BY*) max. =<br />

X*(Y*)-170-A-M/2<br />

150<br />

M<br />

185<br />

NSV0_01034<br />

• Junction units LV, LH <strong>40</strong>0 A<br />

X*(Y*)(X*(Y*) min. =<br />

370+M+A+70)<br />

BX*(BY*) min. =<br />

370+M/2<br />

620 (min.) 450 450<br />

– – –<br />

1250 (max.) 450 1070<br />

BX*(BY*) max. =<br />

X*(Y*)-70-A-M/2<br />

• Junction units LV, LH 1250 A<br />

5<br />

1) Replace the asterisk * according to the table.<br />

Note: With other fire barrier configurations, please contact your<br />

local Siemens sales office.<br />

X*(Y*)(X*(Y*) min. =<br />

370+M+A+130)<br />

BX*(BY*) min. =<br />

370+M/2<br />

680 (min.) 450 450<br />

– – –<br />

1250 (max.) 450 1010<br />

BX*(BY*) max. =<br />

X*(Y*)-130-A-M/2<br />

The dimension X* min or Y* min on the side with corner covering is<br />

550 mm.<br />