Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />
© Siemens AG 2007<br />
Fire barriers<br />
Fire resistance class S120<br />
• Wall thickness M ≥ 150 mm<br />
(distance from wall/inside corner A ≥ 200 mm)<br />
BD2C-...-L... + BD2-S120-BX*(BY*)-M* 1)<br />
• Junction units LL, LR<br />
M 150 A 200<br />
185 185<br />
X*(Y*)(X*(Y*) min. =<br />
370+M+A+170)<br />
BX*(BY*) min. =<br />
370+M/2<br />
890 (min.) 450 450<br />
– – –<br />
1250 (max.) 450 800<br />
• Junction units LV, LH <strong>40</strong>0 A<br />
X*(Y*)(X*(Y*) min. =<br />
370+M+A+70)<br />
BX*(BY*) min. =<br />
370+M/2<br />
790 (min.) 450 450<br />
– – –<br />
1250 (max.) 450 900<br />
BX*(BY*) max. =<br />
X*(Y*)-170-A-M/2<br />
BX*(BY*) max. =<br />
X*(Y*)-70-A-M/2<br />
NSV0_01033<br />
• Junction units LV, LH 1250 A<br />
X*(Y*)(X*(Y*) min. =<br />
370+M+A+130)<br />
BX*(BY*) min. =<br />
370+M/2<br />
850 (min.) 450 450<br />
– – –<br />
1250 (max.) 450 8<strong>40</strong><br />
BX*(BY*) max. =<br />
X*(Y*)-130-A-M/2<br />
Fire resistance class S120<br />
• Wall thickness M ≥ 150 mm<br />
(distance from wall/inside corner 30 mm ≤ A < 200 mm)<br />
BD2C-...-L... + BD2-S120-BX*(BY*)-M* 1)<br />
• Junction units LL, LR<br />
A 30 ... 190<br />
185<br />
X*(Y*)(X*(Y*) min. =<br />
370+M+A+170)<br />
BX*(BY*) min. =<br />
370+M/2<br />
720 (min.) 450 450<br />
– – –<br />
1250 (max.) 450 970<br />
BX*(BY*) max. =<br />
X*(Y*)-170-A-M/2<br />
150<br />
M<br />
185<br />
NSV0_01034<br />
• Junction units LV, LH <strong>40</strong>0 A<br />
X*(Y*)(X*(Y*) min. =<br />
370+M+A+70)<br />
BX*(BY*) min. =<br />
370+M/2<br />
620 (min.) 450 450<br />
– – –<br />
1250 (max.) 450 1070<br />
BX*(BY*) max. =<br />
X*(Y*)-70-A-M/2<br />
• Junction units LV, LH 1250 A<br />
5<br />
1) Replace the asterisk * according to the table.<br />
Note: With other fire barrier configurations, please contact your<br />
local Siemens sales office.<br />
X*(Y*)(X*(Y*) min. =<br />
370+M+A+130)<br />
BX*(BY*) min. =<br />
370+M/2<br />
680 (min.) 450 450<br />
– – –<br />
1250 (max.) 450 1010<br />
BX*(BY*) max. =<br />
X*(Y*)-130-A-M/2<br />
The dimension X* min or Y* min on the side with corner covering is<br />
550 mm.<br />
5/100 Siemens LV 70 · 2006