12.03.2015 Views

BD01 System – 40 ... 160 A - GRUP DAP

BD01 System – 40 ... 160 A - GRUP DAP

BD01 System – 40 ... 160 A - GRUP DAP

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>BD01</strong> <strong>System</strong> — <strong>40</strong> ... <strong>160</strong> A<br />

© Siemens AG 2007<br />

Introduction<br />

■ Overview<br />

2<br />

1<br />

4 5<br />

3<br />

NSV0_00041<br />

4<br />

6<br />

4<br />

Version<br />

Type-tested low-voltage controlgear assembly (TTA)<br />

according to<br />

• IEC/EN 60439-1<br />

• IEC/EN 60439-2<br />

Degree of protection<br />

• High degree of protection IP54 with tap-off points at sides and<br />

bottom<br />

• Degree of protection IP50 with tap-off points at the top<br />

• Degree of protection increase to IP55 with accessories<br />

Components<br />

Trunking units<br />

• 5-wire system<br />

• 2 or 3 outgoing feeders spaced 1 m apart<br />

• 4 or 6 outgoing feeders spaced 0.5 m apart<br />

• Lengths of 2 m and 3 m<br />

Junction units<br />

• Flexible change of direction<br />

4<br />

1 Trunking unit<br />

2 Junction unit<br />

3 Feeder unit<br />

4 Tap-off unit<br />

5 Ancillary equipment unit<br />

6 Optional equipment<br />

Feeder units<br />

• Universal infeed<br />

Tap-off units<br />

• Up to 63 A<br />

• With built-in parts or for customized unit mounting<br />

• For 3, 4 or 8 modular widths (MW)<br />

• Without or with mounting unit<br />

Ancillary equipment units<br />

• For 4 or 8 modular widths (MW)<br />

• Without or with mounting unit<br />

• Without or with socket assembly<br />

Accessories<br />

• Mounting sets for degree of protection IP55<br />

• Fixing and suspending<br />

• Coding set<br />

4/2 Siemens LV 70 · 2006