© Siemens AG 2007<br />

BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />

General data<br />

Feeder units<br />

Conductor cross-sections<br />

Version Type L1, L2, L3 N PE Size of<br />

terminal<br />

Feeder units with terminal<br />

bolt<br />

Center feeder units with<br />

terminal bolts<br />

min.<br />

mm 2<br />

max.<br />

mm 2<br />

BD2.-250-EE (1–3) × 6 1 × 150,<br />

2 × 70<br />

BD2.-<strong>40</strong>0-EE (1–3) × 10 1) 1 × 2<strong>40</strong>,<br />

2 × 120<br />

BD2.-1000-EE (1–3) × 10 1) 2 × 2<strong>40</strong>,<br />

3 × 185<br />

BD2.-1250-EE (1–4) × 10 1) 3 × 300,<br />

4 × 2<strong>40</strong><br />

BD2.-<strong>40</strong>0-ME (1–3) × 10 1) 2 × 2<strong>40</strong>,<br />

3 × 185<br />

BD2.-1000-ME (1–5) × 10 1) (1–5) × 300 (1–5) × 10 1) (1–5) × 300 (1–5) × 10 1) (1–5) × 300 M12<br />

1) Minimum possible cable cross-section for cable lugs.<br />

min.<br />

mm 2<br />

max.<br />

mm 2<br />

(1–3) × 6 1 × 150,<br />

2 × 70<br />

(1–3) × 10 1) 1 × 2<strong>40</strong>,<br />

2 × 120<br />

(1–3) × 10 1) 2 × 2<strong>40</strong>,<br />

3 × 185<br />

(1–4) × 10 1) 3 × 300,<br />

4 × 2<strong>40</strong><br />

(1–3) × 10 1) 2 × 2<strong>40</strong>,<br />

3 × 185<br />

min.<br />

mm 2<br />

max.<br />

mm 2<br />

(1–3) × 6 1 × 150,<br />

2 × 70<br />

(1–3) × 10 1) 1 × 2<strong>40</strong>,<br />

2 × 120<br />

(1–3) × 10 1) 2 × 2<strong>40</strong>,<br />

3 × 185<br />

(1–4) × 10 1) 3 × 300,<br />

4 × 2<strong>40</strong><br />

(1–3) × 10 1) 2 × 2<strong>40</strong>,<br />

3 × 185<br />

screws,<br />

bolts<br />

L1, L2, L3, N, PE<br />

M10<br />

M12<br />

M12<br />

M12<br />

M12<br />

Cable and wiring entries<br />

Type BD2.-250-EE BD2.-<strong>40</strong>0-EE BD2.-1000-EE, BD2.-1000-ME BD2.-1250-EE<br />

BD2.-<strong>40</strong>0-ME<br />

Cable grommets 1 × KT3 1) 2 × KT4 1) 3 × KT4 1) 6 × KT4 1) 4 × KT4 1)<br />

For cable diameter mm 14 ... 54 14 ... 68 14 ... 68 14 ... 68 14 ... 68<br />

1) With strain relief.<br />

Cable entry plate for single core cable<br />

(undrilled cable entry plates)<br />

Type BD2.-250-EE BD2.-<strong>40</strong>0-EE BD2.-1000-EE BD2.-1250-EE<br />

Cable entry plate BD2-250-EBAL BD2-<strong>40</strong>0-EBAL BD2-1000-EBAL BD2-1250-EBAL<br />

Number of cable entries (maximum) 10 × M32, 10 × M<strong>40</strong> 15 × M<strong>40</strong>, 36 × M50<br />

5 × M<strong>40</strong> 6 × M50 and 4 × M<strong>40</strong><br />

Use plastic cable glands with strain relief (not included as standard)<br />

Cable entry plate for single core cable with center feeder units<br />

(undrilled cable entry plates)<br />

Type BD2.-<strong>40</strong>0-ME... BD2.-1000-ME<br />

Cable entry plate BD2-<strong>40</strong>0-MBAL BD2-1000-MBAL<br />

Number of cable entries (maximum) 12 × M<strong>40</strong> and 3 × M32, 31 × M<strong>40</strong>,<br />

6 × M50 and 4 × M<strong>40</strong> 16 × M50 and 4 × M<strong>40</strong><br />

Use plastic cable glands with strain relief (not included as standard)<br />