CD-K <strong>System</strong> — 25 ... <strong>40</strong> A<br />
General data<br />
■ Technical specifications<br />
General technical specifications<br />
Type<br />
Trunking units<br />
CD-K-...<br />
Standards and specifications IEC/EN 60439-1 and -2<br />
Rated insulation voltage U i V AC/DC <strong>40</strong>0/<strong>40</strong>0<br />
Overvoltage category/pollution degree<br />
Rated operational voltage U e V AC <strong>40</strong>0<br />
Frequency Hz 50 ... 60<br />
Resistance to climate Damp heat, constant, according to IEC 60068-2-78<br />
Damp heat, cyclic, according to IEC 60068-2-30<br />
Ambient temperature °C -5 ... +<strong>40</strong><br />
Degree of protection according to IEC/EN 60529<br />
IP54, increase to IP55 with accessories<br />
Material<br />
•Trunking units<br />
Galvanized, painted sheet steel<br />
•Busbars<br />
Tinned and insulated round-section copper wires<br />
Mounting position<br />
Edgewise; tap-off points at the side<br />
Weigth<br />
See "Selection and Ordering Data"<br />
III/3<br />
Type CD-K-1302 CD-K-1303 CD-K-1304 CD-K-2254 (/2)<br />
Conductors<br />
Rated insulation voltage U i V AC/DC <strong>40</strong>0/<strong>40</strong>0 <strong>40</strong>0/<strong>40</strong>0 <strong>40</strong>0/<strong>40</strong>0 <strong>40</strong>0/<strong>40</strong>0<br />
Overvoltage category/pollution degree III/3 III/3 III/3 III/3<br />
Rated operational voltage U e V AC <strong>40</strong>0 <strong>40</strong>0 <strong>40</strong>0 <strong>40</strong>0<br />
Frequency Hz 50 ... 60 50 ... 60 50 ... 60 50 ... 60<br />
Rated current I e = conventional thermal current<br />
A 30 30 30 2 × 25<br />
at max. <strong>40</strong> °C and 35 °C on a 24 h average<br />
Impedance of conductors at 50 Hz<br />
and 20 °C<br />
•Resistance R 20 mΩ/m 5.79 5.79 5.79 4.56<br />
• Reactance X 20 mΩ/m 0.26 0.26 0.26 0.15<br />
• Impedance Z 20 mΩ/m 5.80 5.80 5.80 4.56<br />
Impedance of conductors<br />
under fault conditions<br />
• AC resistance R F mΩ/m 8.24 8.24 8.24 7.50<br />
• Reactance X F mΩ/m 0.44 0.44 0.44 0.32<br />
• Impedance Z F mΩ/m 8.25 8.25 8.25 7.51<br />
Zero impedance according to IEC/EN 60909 (VDE 0102)<br />
•Resistance R 0 Phase to N mΩ/m 24.24 24.24 24.24 18.59<br />
• Reactance X 0 Phase to N mΩ/m 1.77 1.77 1.77 0.82<br />
• Impedance Z 0 Phase to N mΩ/m 24.30 24.30 24.30 18.61<br />
•Resistance R 0 Phase to PE mΩ/m 12.00 12.00 12.00 13.49<br />
• Reactance X 0 Phase to PE mΩ/m 1.80 1.80 1.80 0.82<br />
• Impedance Z 0 Phase to PE mΩ/m 12.13 12.13 12.13 13.52<br />
Short-circuit strength<br />
Rated impulse withstand current I pk kA 2.4 2.4 2.4 3.0<br />
Rated short-time withstand current I cw (t = 1 s) kA 0.56 0.56 0.56 0.69<br />
Rated short-time withstand current I cw (t = 0.1 s) kA 1.6 1.6 1.6 2.0<br />
Conductors<br />
Number of active conductors 2 3 4 2 × 4 (1 × 4, 1 × 2)<br />
Conductor cross-section<br />
• L1, L2, L3 mm 2 3.2 3.2 3.2 4.0<br />
•N mm 2 3.2 3.2 3.2 4.0<br />
• PE (enclosure) = Cu mm 2 11 11 11 11<br />
Conductor material Cu Cu Cu Cu<br />
Fire load kWh/m 0.1 0.15 0.201 0.48<br />
Max. thermal load , I 2 t value A 2 s × 10 3 310 310 310 470<br />
Fixing intervals<br />
m 3 3 3 3<br />
at normal mechanical load<br />
Position of tap-off points<br />
depending on the type: on one side at 0.5 m or 1 m intervals, on both sides at 0.5 m<br />
intervals or alternating from side to side and offset at 0.5 m intervals<br />
3<br />
Siemens LV 70 · 2006<br />
3/7