© Siemens AG 2007<br />

CD-K <strong>System</strong> — 25 ... <strong>40</strong> A<br />

General data<br />

■ Technical specifications<br />

General technical specifications<br />

Type<br />

Trunking units<br />

CD-K-...<br />

Standards and specifications IEC/EN 60439-1 and -2<br />

Rated insulation voltage U i V AC/DC <strong>40</strong>0/<strong>40</strong>0<br />

Overvoltage category/pollution degree<br />

Rated operational voltage U e V AC <strong>40</strong>0<br />

Frequency Hz 50 ... 60<br />

Resistance to climate Damp heat, constant, according to IEC 60068-2-78<br />

Damp heat, cyclic, according to IEC 60068-2-30<br />

Ambient temperature °C -5 ... +<strong>40</strong><br />

Degree of protection according to IEC/EN 60529<br />

IP54, increase to IP55 with accessories<br />

Material<br />

•Trunking units<br />

Galvanized, painted sheet steel<br />

•Busbars<br />

Tinned and insulated round-section copper wires<br />

Mounting position<br />

Edgewise; tap-off points at the side<br />

Weigth<br />

See "Selection and Ordering Data"<br />

III/3<br />

Type CD-K-1302 CD-K-1303 CD-K-1304 CD-K-2254 (/2)<br />

Conductors<br />

Rated insulation voltage U i V AC/DC <strong>40</strong>0/<strong>40</strong>0 <strong>40</strong>0/<strong>40</strong>0 <strong>40</strong>0/<strong>40</strong>0 <strong>40</strong>0/<strong>40</strong>0<br />

Overvoltage category/pollution degree III/3 III/3 III/3 III/3<br />

Rated operational voltage U e V AC <strong>40</strong>0 <strong>40</strong>0 <strong>40</strong>0 <strong>40</strong>0<br />

Frequency Hz 50 ... 60 50 ... 60 50 ... 60 50 ... 60<br />

Rated current I e = conventional thermal current<br />

A 30 30 30 2 × 25<br />

at max. <strong>40</strong> °C and 35 °C on a 24 h average<br />

Impedance of conductors at 50 Hz<br />

and 20 °C<br />

•Resistance R 20 mΩ/m 5.79 5.79 5.79 4.56<br />

• Reactance X 20 mΩ/m 0.26 0.26 0.26 0.15<br />

• Impedance Z 20 mΩ/m 5.80 5.80 5.80 4.56<br />

Impedance of conductors<br />

under fault conditions<br />

• AC resistance R F mΩ/m 8.24 8.24 8.24 7.50<br />

• Reactance X F mΩ/m 0.44 0.44 0.44 0.32<br />

• Impedance Z F mΩ/m 8.25 8.25 8.25 7.51<br />

Zero impedance according to IEC/EN 60909 (VDE 0102)<br />

•Resistance R 0 Phase to N mΩ/m 24.24 24.24 24.24 18.59<br />

• Reactance X 0 Phase to N mΩ/m 1.77 1.77 1.77 0.82<br />

• Impedance Z 0 Phase to N mΩ/m 24.30 24.30 24.30 18.61<br />

•Resistance R 0 Phase to PE mΩ/m 12.00 12.00 12.00 13.49<br />

• Reactance X 0 Phase to PE mΩ/m 1.80 1.80 1.80 0.82<br />

• Impedance Z 0 Phase to PE mΩ/m 12.13 12.13 12.13 13.52<br />

Short-circuit strength<br />

Rated impulse withstand current I pk kA 2.4 2.4 2.4 3.0<br />

Rated short-time withstand current I cw (t = 1 s) kA 0.56 0.56 0.56 0.69<br />

Rated short-time withstand current I cw (t = 0.1 s) kA 1.6 1.6 1.6 2.0<br />

Conductors<br />

Number of active conductors 2 3 4 2 × 4 (1 × 4, 1 × 2)<br />

Conductor cross-section<br />

• L1, L2, L3 mm 2 3.2 3.2 3.2 4.0<br />

•N mm 2 3.2 3.2 3.2 4.0<br />

• PE (enclosure) = Cu mm 2 11 11 11 11<br />

Conductor material Cu Cu Cu Cu<br />

Fire load kWh/m 0.1 0.15 0.201 0.48<br />

Max. thermal load , I 2 t value A 2 s × 10 3 310 310 310 470<br />

Fixing intervals<br />

m 3 3 3 3<br />

at normal mechanical load<br />

Position of tap-off points<br />

depending on the type: on one side at 0.5 m or 1 m intervals, on both sides at 0.5 m<br />

intervals or alternating from side to side and offset at 0.5 m intervals<br />

3<br />

Siemens LV 70 · 2006<br />

3/7