■ Overview<br />

General requirements<br />

The German state building authorities demand that buildings are<br />

designed so that "spreading of fire and smoke is prevented, and<br />

that effective fire fighting and rescue of persons and domestic<br />

animals is facilitated". Fire or flue gas may not spread from one<br />

storey or fire area to another.<br />

All BD2A/BD2C busbar trunking systems can be equipped with<br />

a fire barrier and generally comply with the standards for buildings<br />

including high-rise buildings. The busbar trunking system is<br />

supplied ex-works with fire barriers. Retrofitting is not possible.<br />

A general approval from the German Institute for Building<br />

Engineering (Deutsches Institut für Bautechnik in Berlin DIBt) in<br />

Berlin is available:<br />

• BD2-S120: No. Z-19.15-1046,<br />

• BD2-S90: No. Z-19.15-1048).<br />

The fire resistance class with the BD2 system corresponds with<br />

version S90 or S120 according to DIN 4102 Part 9. The<br />

demands for verification of fire resistance duration at 120 min as<br />

specified to ISO 834 according to IEC/EN 60439-2 are fulfilled.<br />

The requirements for a busbar trunking system as specified to<br />

DIN 4102 are shown in the illustration.<br />

4<br />

3<br />

1<br />

• The center of the fire barrier in the trunking unit must be positioned<br />

in the center of the fire wall or ceiling.<br />

Exception: With junction units, this may not be possible due to<br />

insufficient distance from the wall or ceiling, i.e. the center of<br />

the fire barrier may not coincide with the center of the fire wall<br />

or ceiling. In such cases, PROMATECT-H(L) panels are added<br />

to achieve the actually required wall or ceiling thickness.<br />

• The following information must be provided: For BX*, BY* or<br />

BZ* trunking units, position of the center of the fire barrier in<br />

the trunking unit (or the center of the fire wall or ceiling for junction<br />

units with insufficient distance from the wall or ceiling); the<br />

desired fire resistance rating S90 or S120; and the thickness<br />

M* of the wall or ceiling.<br />

• There are no tap-off points in the area covered by the fire barrier.<br />

• The trunking units must be installed by an approved fire<br />

protection installation specialist.<br />

Notes<br />

For BX* and BY*, replace the asterisk in the type reference by the<br />

required dimension in meters from the center of the clamp terminal<br />

(end without clamp terminal) to the center of the fire wall or<br />

ceiling; for -M* specify the wall or ceiling thickness.<br />

For BZ*, replace the asterisk in the type reference by the required<br />

dimension in meters from the outside edge of limb X to<br />

the center of the fire wall or ceiling; for -M* specify the wall or<br />

ceiling thickness.<br />

1<br />

2<br />

BX*, BY*, BZ*<br />

M*<br />

1 Center line of fire barrier<br />

Positioning in the fire wall<br />

5<br />

NSV0_01070<br />

(1) Permissible temperature increase on components max. 180 °C<br />

(2) Scene of fire: Application of fire according to the standard<br />

temperature curve DIN 4102, Sheet 2<br />

(3) Permitted temperature increase of escaping air: max. 1<strong>40</strong> °C<br />

(4) No flammable gases are permitted to escape. No rescue work may<br />

be hindered by emerging smoke.<br />

Engineering<br />

To ensure fire protection to S90 or S120, the following points<br />

must be observed when engineering and installing trunking and<br />

junction units with fire barriers:<br />

M*<br />

BX*, BY*, BZ*<br />

1<br />

1 Center line of fire barrier<br />

Positioning in the fire ceiling<br />