12.03.2015 Views

BD01 System – 40 ... 160 A - GRUP DAP

BD01 System – 40 ... 160 A - GRUP DAP

BD01 System – 40 ... 160 A - GRUP DAP

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />

© Siemens AG 2007<br />

Fire barriers<br />

Fire resistance class S120<br />

• Wall thickness M ≥ 150 mm BD2C-...-S(W). + BD2-S120-BX*-M* 1)<br />

150<br />

185<br />

L (L min. = 7<strong>40</strong>+M) BX* min. = 370+M/2 BX*max. = L–BX* min.<br />

900 (min.) 450 450<br />

– – –<br />

– – –<br />

3250 (max.) 450 2800<br />

185<br />

M<br />

NSV0_01023<br />

1) Replace the asterisk * according to the table.<br />

Position of the fire barrier on junction units<br />

The minimum dimensions applicable for positioning fire barriers<br />

on the limbs of junction units differ, depending on the routing of<br />

the trunking and the distance from the fire wall to the inside edge<br />

of the trunking unit.<br />

Y* (X*)<br />

NSV0_01025<br />

BY* (BX*)<br />

Y* (X*)<br />

X* (Y*)<br />

BY* (BX*)<br />

170<br />

NSV0_01024<br />

c<br />

X* (Y*)<br />

e <strong>160</strong> ... <strong>40</strong>0 A 500 ... 1250 A<br />

c 70<br />

130<br />

Elbow, type: BD2A-...-LR(L)-X* (Y*), +BD2-S90(S120)-BX*(BY*)-M*<br />

BD2C-...-LR(L)-X* (Y*), +BD2-S120-BX*(BY*)-M*<br />

Knee, type:<br />

BD2A-...-LV(H)-X* (Y*), +BD2-S90(S120)-BX*(BY*)-M*<br />

BD2C-...-LV(H)-X* (Y*), +BD2-S120-BX*(BY*)-M*<br />

Fire resistance class S90<br />

• Wall thickness 150 mm ≤ M < 250 mm<br />

(distance from wall/inside corner A ≥ 200 mm)<br />

BD2A-...-L... + BD2-S90-BX*(BY*)-M* 1)<br />

• Junction units LL, LR<br />

X*(Y*)(X*(Y*) min. =<br />

185+M+A+170)<br />

BX*(BY*) min. =<br />

185+M/2<br />

710 (min.) 260 260<br />

BX*(BY*) max. =<br />

X*(Y*)-170-A-M/2<br />

– – –<br />

5<br />

A 200<br />

150 M < 250<br />

NSV0_01026<br />

1250 (max.) 260 800<br />

• Junction units LV, LH <strong>40</strong>0 A<br />

X*(Y*)(X*(Y*) min. =<br />

185+M+A+70)<br />

BX*(BY*) min. =<br />

185+M/2<br />

610 (min.) 260 260<br />

– – –<br />

1250 (max.) 260 900<br />

• Junction units LV, LH 1000 A<br />

BX*(BY*) max. =<br />

X*(Y*)-70-A-M/2<br />

X*(Y*)(X*(Y*) min. =<br />

185+M+A+130)<br />

BX*(BY*) min. =<br />

185+M/2<br />

670 (min.) 260 260<br />

BX*(BY*) max. =<br />

X*(Y*)-130-A-M/2<br />

– – –<br />

1250 (max.) 260 8<strong>40</strong><br />

1) Replace the asterisk * according to the table.<br />

5/96 Siemens LV 70 · 2006