© Siemens AG 2007<br />

BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />

Fire barriers<br />

■ Design<br />

Position of fire barrier on the trunking unit<br />

L<br />

250<br />

NSV0_01019<br />

BX*<br />

Type:<br />

BD2A-...-S(W).-. + BD2-S90(S120)-BX*-M*<br />

BD2C-...-S(W).-. + BD2-S120-BX*-M*<br />

Fire resistance class S90<br />

• Wall thickness M ≥ 150 mm BD2A-...-S(W). + BD2-S90-BX*-M* 1)<br />

150<br />

L (L min. = 370+M) BX* min. = 185+M/2 BX*max. = L–BX* min.<br />

520 (min.) 260 260<br />

– – –<br />

– – –<br />

3250 (max.) 260 2980<br />

M<br />

NSV0_01020<br />

Fire resistance class S120<br />

• Wall thickness 150 mm ≤ M < 250 mm BD2A-...-S(W). + BD2-S120-BX*-M* 1)<br />

M = 150 ... 250<br />

100<br />

100<br />

L (L min. = 570+M) BX* min. = 285+M/2 BX*max. = L–BX* min.<br />

720 (min.) 360 360<br />

– – –<br />

– – –<br />

3250 (max.) 360 2890<br />

NSV0_01021<br />

• Wall thickness M ≥ 250 mm BD2A-...-S(W). + BD2-S120-BX*-M* 1)<br />

L (L min. = 370+M) BX* min. = 185+M/2 BX*max. = L–BX* min.<br />

620 (min.) 310 310<br />

– – –<br />

– – –<br />

250<br />

3250 (max.) 310 29<strong>40</strong><br />

5<br />

M<br />

NSV0_01022<br />

1) Replace the asterisk * according to the table.<br />