© Siemens AG 2007<br />

BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />

General data<br />

Trunking units with copper conductor<br />

Type BD2C-.-<strong>160</strong> BD2C-.-250 BD2C-.-315 BD2C-.-<strong>40</strong>0<br />

Conductors<br />

Rated insulation voltage U i V AC/DC 690/800 690/800 690/800 690/800<br />

Overvoltage category/pollution degree III/3 III/3 III/3 III/3<br />

Rated operational voltage U e V AC 690 690 690 690<br />

Frequency Hz 50 ... 60 50 ... 60 50 ... 60 50 ... 60<br />

Rated current I e = thermal rated current at<br />

A <strong>160</strong> 250 315 <strong>40</strong>0<br />

max. <strong>40</strong> °C and 35 °C on 24 h average<br />

Impedance per unit length of current paths with 50 Hz and<br />

20 °C ambient temperature (cold rails)<br />

•Resistance R 20 mΩ/m 0.303 0.295 0.295 0.180<br />

• Reactance X 20 mΩ/m 0.157 0.158 0.123 0.114<br />

• Impedance Z 20 mΩ/m 0.341 0.334 0.316 0.213<br />

Impedance per unit length of current paths with 50 Hz and<br />

20 °C ambient temperature (rail under operating conditions<br />

warm)<br />

•Resistance R 1 mΩ/m 0.333 0.383 0.383 0.239<br />

• Reactance X 1 mΩ/m 0.157 0.158 0.112 0.115<br />

• Impedance Z 1 mΩ/m 0.368 0.414 0.399 0.266<br />

Impedance of conductors under fault conditions<br />

• AC resistance per unit length R F mΩ/m 0.666 0.674 0.664 0.548<br />

• Reactance per unit length X F mΩ/m 0.511 0.530 0.436 0.446<br />

• Impedance per unit length Z F mΩ/m 0.839 0.857 0.795 0.706<br />

Zero impedance according to IEC/EN 60909 Phase to N R 0 mΩ/m 1.419 1.429 1.301 1.191<br />

(VDE 0102)<br />

X 0 mΩ/m 0.691 0.702 0.590 0.632<br />

Z 0 mΩ/m 1.579 1.592 1.458 1.349<br />

Phase to PE R 0 mΩ/m 1.027 1.139 1.065 0.956<br />

X 0 mΩ/m 0.641 0.529 0.507 0.507<br />

Z 0 mΩ/m 1.211 1.256 1.179 1.082<br />

Short-circuit strength<br />

• Rated impulse withstand current I pk kA 17 32 36 <strong>40</strong><br />

• Rated short-time withstand current I cw t = 1 s kA 5.5 10 14 16<br />

t = 0.1 s kA 10 16 18 20<br />

Number of conductors 5 5 5 5<br />

Conductor cross-section L1, L2, L3 mm 2 63 63 66 108<br />

N mm 2 63 63 66 108<br />

PE mm 2 63 63 66 108<br />

1 / 2 PE mm 2 63 63 66 66<br />

Conductor material Cu Cu Cu Cu<br />

Max. interval between trunking units<br />

at normal mechanical loading<br />

•Edgewise m 4 4 4 4<br />

• Edgewise with BD2-BD 1) m 4 4 4 4<br />

•Flat m 3.5 3.5 3.5 3.5<br />

Fire load 2) kWh/m 1.32 1.32 1.32 1.32<br />

1) When using BD2-BD spacer bracket.<br />

2) Values for trunking units with tap-off points.<br />

For more values, see page 5/21.<br />

5<br />

Siemens LV 70 · 2006<br />