© Siemens AG 2007<br />
CD-K <strong>System</strong> — 25 ... <strong>40</strong> A<br />
Introduction<br />
Version<br />
Type-tested low-voltage controlgear assembly (TTA)<br />
according to<br />
• IEC/EN 60439-1<br />
• IEC/EN 60439-2<br />
Degree of protection<br />
• High degree of protection to IP54 of the standard version<br />
• Increase to IP55 with accessories<br />
Components<br />
■ Design<br />
Trunking units<br />
3 2 1<br />
NSV0_00001<br />
Trunking units<br />
• 3-, 4-, 5- and 3/5-conductor system<br />
• Equipment on one side:<br />
- 2 or 3 outgoing feeders spaced 1 m apart<br />
- 5 outgoing feeders spaced 0.5 m apart<br />
• Equipment on two sides:<br />
- 2, 3 or 5 outgoing feeders spaced 1 m apart<br />
- 2, 3 or 5 outgoing feeders spaced 0.5 m apart<br />
• Lengths of 2 m and 3 m<br />
• Plug-in connection<br />
• Codable tap-off points<br />
Feeder units<br />
• Entry feeder units<br />
• End feeder units<br />
Tap-off plugs<br />
• 3-pole, 10 A and 16 A, Lx (phase can be plugged over<br />
optionally to L1, L2, L3 ), N and PE<br />
• 5-pole, 10 A and 16 A, L1, L2, L3, N, PE<br />
Accessories<br />
•End flange<br />
• Fixing bracket<br />
• Suspension hook<br />
• Suspension bracket<br />
• Cable fixture<br />
•Coding set<br />
• Degree of protection IP55<br />
1 Locating section<br />
2 Connection terminal<br />
3 Tap-off point<br />
The trunking units are available in lengths of 2 m and 3 m. They<br />
consist of a rectangular, galvanized metal enclosure with a<br />
white-gray paint finish.<br />
They are equipped on one side or two sides with current leads:<br />
• 2 leads for L1 + N (PE = enclosure)<br />
• 3 leads for L1 + L2 + N (PE = enclosure)<br />
• 4 leads for L1 + L2 + L3 + N (PE = enclosure)<br />
Single conductor run:<br />
tap-off points at intervals<br />
of 0,5 or 1 m<br />
The tap-off points are spaced at regular intervals of 0.5 or 1 m on<br />
the trunking unit.<br />
The trunking unit enclosure acts as the PE conductor. Three<br />
current ratings are available: 2 × 25 A, 30 A, <strong>40</strong> A and 2 × <strong>40</strong> A.<br />
All trunking units have finger-safe tap-off points, that can be<br />
coded by the user.<br />
Connections<br />
NSV0_00002<br />
Two conductor runs:<br />
tap-off points at intervals<br />
of 0,5 or 1 m<br />
3<br />
■ Benefits<br />
7 Lower planning costs through simple configuration<br />
7 Quick-release plug-in connection for fast assembly<br />
7 Tap-off points on both sides for optimized utilization of the<br />
busbar<br />
7 Uniform current loading of the conductors through splitting of<br />
the tap-off plugs among the individual phases<br />
7 Tap-off plugs allow fast and flexible load relocation<br />
7 Accessories for increasing the degree of protection to IP55 for<br />
extreme environmental conditions<br />
NSV0_00003<br />
The trunking units, including those with feeder units and flanges,<br />
are assembled without tools by straightforward plug-in connection.<br />
The PE path is established automatically when the enclosures<br />
are connected.<br />
An interlock mechanism with two fixings prevents a loosening of<br />
the connections between the trunking units, Two fixtures prevent<br />
self-disconnection of the connection. No expansion compensation<br />
is required.<br />
Siemens LV 70 · 2006<br />
3/3