© Siemens AG 2007<br />

CD-K <strong>System</strong> — 25 ... <strong>40</strong> A<br />

Introduction<br />

Version<br />

Type-tested low-voltage controlgear assembly (TTA)<br />

according to<br />

• IEC/EN 60439-1<br />

• IEC/EN 60439-2<br />

Degree of protection<br />

• High degree of protection to IP54 of the standard version<br />

• Increase to IP55 with accessories<br />

Components<br />

■ Design<br />

Trunking units<br />

3 2 1<br />

NSV0_00001<br />

Trunking units<br />

• 3-, 4-, 5- and 3/5-conductor system<br />

• Equipment on one side:<br />

- 2 or 3 outgoing feeders spaced 1 m apart<br />

- 5 outgoing feeders spaced 0.5 m apart<br />

• Equipment on two sides:<br />

- 2, 3 or 5 outgoing feeders spaced 1 m apart<br />

- 2, 3 or 5 outgoing feeders spaced 0.5 m apart<br />

• Lengths of 2 m and 3 m<br />

• Plug-in connection<br />

• Codable tap-off points<br />

Feeder units<br />

• Entry feeder units<br />

• End feeder units<br />

Tap-off plugs<br />

• 3-pole, 10 A and 16 A, Lx (phase can be plugged over<br />

optionally to L1, L2, L3 ), N and PE<br />

• 5-pole, 10 A and 16 A, L1, L2, L3, N, PE<br />

Accessories<br />

•End flange<br />

• Fixing bracket<br />

• Suspension hook<br />

• Suspension bracket<br />

• Cable fixture<br />

•Coding set<br />

• Degree of protection IP55<br />

1 Locating section<br />

2 Connection terminal<br />

3 Tap-off point<br />

The trunking units are available in lengths of 2 m and 3 m. They<br />

consist of a rectangular, galvanized metal enclosure with a<br />

white-gray paint finish.<br />

They are equipped on one side or two sides with current leads:<br />

• 2 leads for L1 + N (PE = enclosure)<br />

• 3 leads for L1 + L2 + N (PE = enclosure)<br />

• 4 leads for L1 + L2 + L3 + N (PE = enclosure)<br />

Single conductor run:<br />

tap-off points at intervals<br />

of 0,5 or 1 m<br />

The tap-off points are spaced at regular intervals of 0.5 or 1 m on<br />

the trunking unit.<br />

The trunking unit enclosure acts as the PE conductor. Three<br />

current ratings are available: 2 × 25 A, 30 A, <strong>40</strong> A and 2 × <strong>40</strong> A.<br />

All trunking units have finger-safe tap-off points, that can be<br />

coded by the user.<br />

Connections<br />

NSV0_00002<br />

Two conductor runs:<br />

tap-off points at intervals<br />

of 0,5 or 1 m<br />

3<br />

■ Benefits<br />

7 Lower planning costs through simple configuration<br />

7 Quick-release plug-in connection for fast assembly<br />

7 Tap-off points on both sides for optimized utilization of the<br />

busbar<br />

7 Uniform current loading of the conductors through splitting of<br />

the tap-off plugs among the individual phases<br />

7 Tap-off plugs allow fast and flexible load relocation<br />

7 Accessories for increasing the degree of protection to IP55 for<br />

extreme environmental conditions<br />

NSV0_00003<br />

The trunking units, including those with feeder units and flanges,<br />

are assembled without tools by straightforward plug-in connection.<br />

The PE path is established automatically when the enclosures<br />

are connected.<br />

An interlock mechanism with two fixings prevents a loosening of<br />

the connections between the trunking units, Two fixtures prevent<br />

self-disconnection of the connection. No expansion compensation<br />

is required.<br />