BD2 <strong>System</strong> — <strong>160</strong> ... 1250 A<br />

© Siemens AG 2007<br />

Introduction<br />

BD2-AK03 tap-off units up to 125 A<br />

with circuit-breakers, fuse switch-disconnectors, fuse bases,<br />

miniature circuit-breakers and fuse-switches<br />

Features:<br />

• On versions with fuse switch-disconnectors or circuit-breakers,<br />

the cover is interlocked with these switches and can<br />

therefore be opened only when they are switched off.<br />

• Terminal bolts for cables<br />

• Miniature circuit-breakers can optionally be operated from the<br />

outside (mounting unit with 8 MW; 1 MW = 18 mm)<br />

• On versions with fuse switch-disconnectors or circuit-breakers,<br />

the cover is interlocked with these switches and can<br />

therefore be opened only when they are switched off.<br />

• On versions with fuse bases, the load must be disconnected<br />

before the enclosure cover is removed.<br />

• Connections for multi-core or single-core cables are possible.<br />

NSV0_00132<br />

5<br />

BD2-AK03X/L...<br />

Tap-off units BD2-AK02 up to 63 A and BD2-AK03 up to 125 A<br />

configured to customer specifications<br />

Features:<br />

• Device installation to customer specification in compliance<br />

with the requirements for type-tested low-voltage switchgear<br />

and controlgear assemblies (TTA). Engineering, quotations<br />

and delivery through your Siemens contacts in our branches.<br />

• Devices mounted on pre-drilled mounting plates, module<br />

mounting rails or top-hat rails according to EN 60715<br />

NSV0_00133<br />

BD2-AK03...<br />

Steel enclosed tap-off units BD2-AK04 up to 250 A and<br />

BD2-AK05 up to <strong>40</strong>0 A and BD2-AK06 up to 630 A<br />

without cover-integrated switch-disconnector<br />

Tap-off units BD2-AK04 up to 250 A,<br />

BD2-AK05 up to <strong>40</strong>0 A and AK06 up to 630 A<br />

with circuit-breakers, fuse switch-disconnectors and fuse bases<br />

Features:<br />

• Type BD2-AK05 and BD2-AK06 tap-off units > 250 A can be<br />

mounted only on 500 A to 1250 A trunking units.<br />

• Hot-galvanized and powder-coated sheet-steel enclosure,<br />

color light gray, RAL 7035.<br />

• The tap-off units can be mounted and removed only with their<br />

cover open.<br />

• An anti-rotation feature prevents incorrect mounting.<br />

• Cables can be introduced from three sides; use plastic cable<br />

glands with strain relief (not supplied).<br />

• Power pick-up through silver-plated lyra-shaped contacts<br />

• If the PE conductor is used as a PEN conductor, note that the<br />

PE contact of the BD2-AK04, BD2-AK05 and BD2-AK06 tapoff<br />

units have only half the cross-section and therefore cannot<br />

carry the full rated current.<br />

• The connection cable should be supported separately if<br />

required.<br />

BD2-AK05/LS...<br />

Ancillary equipment units<br />

Features:<br />

• The enclosure is made from hot-galvanized sheet steel.<br />

• Cables can be introduced from 4 sides (use plastic cable<br />

glands with strain relief; not supplied).<br />

• Can be combined with tap-off units (BD2-AK02, AK2, AK03,<br />

AK3)<br />

• A standard mounting rail is built-in for component mounting.<br />

• 1 size with 8 MW (1 MW = 18 mm; MW = modular width)<br />

• Without or with mounting unit for external<br />

operation (1 size with 8 MW)<br />

• Installation of devices (e.g. miniature circuit-breakers) in accordance<br />

with DIN 43871 possible up to and including 63 A.<br />

BD2-GKM2/F<br />

NSV0_01014<br />

NSV0_00139<br />

5/10 Siemens LV 70 · 2006