<strong>BD01</strong> <strong>System</strong> — <strong>40</strong> ... <strong>160</strong> A<br />
Introduction<br />
Universal fixing bracket<br />
The universal fixing brackets can be used for wall and ceiling<br />
mounting. The maximum fixing interval at normal mechanical<br />
loads is 3 m for edgewise and 1.5 m for flat mounting.<br />
At higher mechanical loads (e.g. pulling of plugs), an intermediate<br />
support with an additional fixing bracket at the trunking unit<br />
is recommended.<br />
Once the fixing point is decided, the tabs on the fixing bracket<br />
are pushed in to fix the trunking run.<br />
Coding<br />
The systems can be coded for different frequencies or voltages.<br />
For this purpose, the <strong>BD01</strong>-K coding set can be fitted by the user<br />
to the installed system at each tap-off point. Four coding positions<br />
are possible.<br />
NSV0_00063<br />
NSV0_00060<br />
Tap-off units can be coded on site by adapting the front.<br />
<strong>BD01</strong>-B<br />
Fixing brackets<br />
These fixing brackets can be used for suspension of<br />
flat-mounted trunking units. Also they can be fastened at the<br />
connection points in order to increase the mechanical rigidity of<br />
the trunking units.<br />
NSV0_00064<br />
<strong>BD01</strong>-BAP<br />
Suspension bracket<br />
The suspension brackets can be used for wall, ceiling and suspension<br />
mounting of the system. They can be fitted at any point<br />
of the trunking unit. The maximum fixing interval at normal mechanical<br />
loads is 3 m for edgewise and 1.5 m for flat mounting.<br />
At higher mechanical loads (e.g.pulling of plugs), an intermediate<br />
support with an additional fixing bracket at the trunking unit<br />
is recommended.<br />
NSV0_00061<br />
Sealing<br />
Every tap-off point on the trunking unit can be sealed.<br />
Feeder, junction, tap-off and ancillary equipment units can be<br />
made sealable with additional components (please enquire).<br />
Cable glands<br />
For the feeder, tap-off and ancillary equipment units, use plastic<br />
cable glands with strain relief (not included as standard).<br />
Terminals<br />
We recommend the use of Weidmüller or Phoenix screw terminals<br />
for the N and PE conductor connections in tap-off and<br />
ancillary equipment units.<br />