4.1.2 Environment<br />
4.1.2.1 Climatic Conditions<br />
4.1.2.2 Vibration<br />
4.1.2.3 Site<br />
- Operation<br />
• Temperature: for maximum reliability, it is recommended you comply with an ambient<br />
temperature of between 5 and 40 degrees Celsius, with a maximum variation of 5<br />
degrees Celsius per hour.<br />
• Humidity: the humidity must be in the range 10% - 80% (no condensation) with a<br />
maximum variation of 10% per hour.<br />
- Storage<br />
• Temperature: the temperature must be kept between -20 and +70 degrees Celsius.<br />
• Humidity: the humidity must be kept in the range 10 - 95% (no condensation).<br />
No vibration, even intermittent, may be transmitted to the equipment when running.<br />
- Choose a dry, clean and well ventilated location.<br />
- Maintain an ambient air flow to ensure normal ventilation. If the air flow is blocked or<br />
restricted, of the incoming air is too hot, overheating is possible.<br />
- When installing the equipment in an enclosed 19" rack, verify that the rack is provided with<br />
a fan suited to the heat dissipation of the equipment installed. Maintain a minimum gap of 3<br />
cm around the side ventilation holes (left and right sides), and of 10 cm minimum around<br />
the ventilation holes at the rear of the equipment. Verify that the air flow is not impeded on<br />
the sides of the rack.<br />
- When fixing the system directly to the wall using the wall-mounting kit (OmniPCX Office<br />
RCE Small and OmniPCX Office RCE Medium platforms only), maintain a free space of at<br />
least 15 cm around the whole system. Ensure that no objects are placed on the upper part<br />
of the system to restrict the extraction of hot air. When installing several platforms, it is<br />
preferable to align then horizontally. When superposing them vertically, they should be<br />
separated by at least 10 cm.<br />
- Verify that the cables connecting the Alcatel-Lucent OmniPCX Office Communication<br />
Server or other equipment, or the supports for the housing structure (19" rack for example)<br />
do not obstruct the air flow through the platform.<br />
- A switchable 230 V or 110 V mains socket (according to country) - 50Hz (LNE) is required<br />
at less than 1 m from the platform unless it is installed in a rack in which case the<br />
integrated circuit breaker is used.<br />
- Adequate lighting must be provided.<br />
4.2 Connections and Cabling<br />
4.2.1 Detailed description<br />
4.2.1.1 Output Connectors<br />
4-3