11 Manual Reset (3) Man Rset Bias applied to<br />
output power,<br />
expressed as a<br />
percentage of<br />
output power<br />
12 Hysteresis (7) Hyst 1 Defines band<br />
below setpoint<br />
where output 1<br />
will not<br />
transition<br />
13 Hysteresis (7,2) Hyst 2 Defines band<br />
above setpoint<br />
where output 2<br />
will not<br />
transition<br />
14 Setpoint Rate SP Rate Determines<br />
maximum rate<br />
of change for<br />
setpoint in units<br />
per hour<br />
15 Output 1 Cycle<br />
Time (6)<br />
16 Output 2 Cycle<br />
Time (6,2)<br />
CycTime1<br />
CycTime2<br />
Limits<br />
frequency of<br />
operation of<br />
output relay to<br />
maximize relay<br />
life<br />
Limits<br />
frequency of<br />
operation of<br />
output relay to<br />
maximize relay<br />
life<br />
0% to 100%<br />
(Output1 only)<br />
-100% to<br />
+100%<br />
(Output 1 &<br />
Output 2)<br />
Default 25%<br />
0.1 to 10% of<br />
input span<br />
Default 0.5%<br />
(=7°F for input<br />
type 1420)<br />
0.1 to 10% of<br />
input span<br />
Default 0.5%<br />
(=7°F for input<br />
type 1420)<br />
1 to 9999, INF<br />
Default = INF<br />
(infinite)<br />
0.5, 1, 2, 4, 8,<br />
16, 32, 64,<br />
128, 256 or<br />
512 seconds.<br />
Default = 1<br />
second<br />
0.5, 1, 2, 4, 8,<br />
16, 32, 64,<br />
128, 256 or<br />
512 seconds.<br />
Default = 1<br />
second<br />
17 Motor Travel<br />
Time (8)<br />
MT Time<br />
Time Taken for<br />
value to travel<br />
from one end<br />
stop to the<br />
other<br />
5 seconds to 5<br />
minutes<br />
Default = 1.00<br />
Minute<br />
Edition 1<br />
45 MIC 1462 Manual