Alarms<br />
Maximum Number:<br />
Maximum # Outputs:<br />
Combination Alarms:<br />
Hysteresis:<br />
Loop Alarm:<br />
Two "soft" alarms plus Loop Alarm<br />
Up to 2 outputs can be used for alarm<br />
purposes<br />
Logical OR or AND of alarms to an individual<br />
hardware output is available.<br />
1 LSD to 10% of span.<br />
Detects faults in the control feedback loop by<br />
continuously monitoring process variable<br />
response to the control output(s).<br />
PROGRAM SPECIFICATIONS<br />
Programs:<br />
Eight, each with free-form segments<br />
Length of Programs: Adjustable in the range 1 to 16 segments;<br />
programs cascadable - maximum length 121<br />
segments.<br />
Segment Types: Ramp, Dwell, Join, Repeat, or End.<br />
Program Cycling: Range 1 to 9999, infinite.<br />
Delayed Start: May be set in the range 0 to 99:59 (hours:minutes).<br />
One setting applies to all programs.<br />
Control:<br />
Run, Hold, Abort, Time Base x60 (local or remote);<br />
Select Program (local or remote); Jump to next<br />
Segment.<br />
Start From:<br />
Either current process variable value or controller<br />
setpoint value.<br />
Go To:<br />
Base Mode or Off Mode<br />
End On:<br />
Final Value or controller setpoint.<br />
Deviation/Hold: Off, below setpoint only, above setpoint only or<br />
above and below setpoint. On ramps only, on<br />
dwells only, or on both ramps and dwells. Auto/<br />
Hold band may be set from 0 to input span.<br />
Time Base:<br />
Either hours:minutes or minutes:secs (x60) preprogrammable<br />
or may be set during Program Run.<br />
Segment Time: May be set in the range 0 to 99:59 (hours:minutes<br />
or minutes:seconds).<br />
Ramp Rate: 0 to 9999 least significant digits per hour or minute.<br />
Edition 1<br />
93 MIC 1462 Manual