01.07.2015 Views

MIC1462 manual.pdf

MIC1462 manual.pdf

MIC1462 manual.pdf

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

MESSAGE<br />

AVAILABLE<br />

STEP DESCRIPTION DISPLAY FUNCTION SETTING<br />

3 Alarm Inhibit Inhibit Specifies which nonE-None<br />

alarms are ALA1-Alarm 1<br />

inhibited ALA2-Alarm 2<br />

both-Both<br />

Alarms<br />

4a Process High HiAlarm 1 If Alarm 1 is a Input Range<br />

Alarm 1 value process high Max to input<br />

alarm, process Range Min.<br />

variable at or Default=Input<br />

above which Range Max.<br />

Alarm 1 will<br />

be active<br />

4b Process Low LoAlarm 1 If Alarm 1 is a Input Range<br />

Alarm 1 value process low Max to input<br />

alarm, process Range Min.<br />

variable at or Default=Input<br />

below which Range Min.<br />

Alarm 1 will<br />

be active<br />

4c Band Alarm 1 BaAlarm1 If Alarm 1 is a ±(Input Span)<br />

Value<br />

Band Alarm, the From setpoint<br />

band of process Default = five<br />

variable values input units<br />

(centered on the<br />

setpoint) outside<br />

which the process<br />

variable will<br />

cause the alarm<br />

to be active<br />

MIC 1462 Manual 50<br />

Edition 1