DC<br />
Resolution:<br />
Eight bits in 250mS (10 bits in 1 second typical,<br />
>10 bits in >1 second typical).<br />
Update Rate: Four times per second<br />
Ranges: * 0-20mA, 4-20mA, 0-10V, and 0-5V<br />
Load Impedance: 0-20mA: 500 ohm maximum<br />
4-20mA: 500 ohm maximum<br />
0-10V: 500 ohm minimum<br />
0-5V: 500 ohm minimum<br />
Isolation:<br />
Isolated from all other inputs and outputs.<br />
* Changes between V and mA ranges also require jumper movement.<br />
TRANSMITTER POWER SUPPLY<br />
Output:<br />
20-28VDC (24VDC nominal)<br />
Min. Load Impedance: 910 ohm (22mA @ 20VDC)<br />
CONTROL SPECIFICATIONS<br />
Control Types:<br />
PID, PID/ON-OFF2, ON-OFF<br />
Automatic Tuning Types: Pre-Tune and Auto-Tune<br />
Proportional Bands: 0 (OFF), 0.5% - 999.9% of input span @ 0.1%<br />
increments<br />
Auto Reset:<br />
1s-99min 59sec/repeat and OFF<br />
Rate:<br />
0 (OFF) - 99min 59sec<br />
Manual Reset (Bias): Adjustable in the range 0-100% of output<br />
power (single output) or -100% to +100% of<br />
output power (dual output)<br />
Deadband/Overlap: -20% to +20% of proportional band 1 +<br />
proportional band 2<br />
ON/OFF Hysteresis: 0.1% to 10.0% of input span<br />
Auto/Manual Control: User-selectable with "bumpless" transfer into<br />
and out of Manual control.<br />
Cycle Times:<br />
Selectable from 0.5sec to 512sec in binary<br />
steps<br />
Setpoint Range:<br />
Limited by Setpoint Maximum and Setpoint<br />
Minimum.<br />
Setpoint Maximum: Limited by Setpoint and Range Maximum.<br />
Setpoint Minimum: Limited by Range Minimum and Setpoint.<br />
MIC 1462 Manual 92<br />
Edition 1