AKD <strong>Installation</strong> | 8 Electrical <strong>Installation</strong>8.16.5.2 FAULT relay contactsOperational readiness (terminals X8/1 and X8/2 ) is signaled by a floating relay contact.The fault relay can be programmed to two modes of operation:- Contact closed when there is no fault- Contact closed when there is no fault and the drive is enabled.The signal is not influenced by the enable signal, the I²t-limit, or the brake threshold.Technical characteristics• FAULT: Relay output, max. 30 Vdc or 42 Vac, 1 A• Time to close: max. 10 ms• Time to open: max. 10 msAll faults cause the FAULT contact to open and the output stage to be switchedoff (if the FAULT contact is open, the output stage is inhibited -> no power output).List of the fault messages: see page 136.Wiring diagram120 Kollmorgen | December 2009