User <strong>Manual</strong> <strong>T*SOL</strong> 7 System Definition<br />

Here, you can enter the temperature to which the tank is to be heated. In addition, you can enter the<br />

time and duration of validity of these control parameters. The maximum operating time is relevant in<br />

the event that the set temperature is not reached.<br />

The entries in the image show that the tank is heated to 60 °C every day at 3.00 pm, maintained at this<br />

temperature for 60 minutes, and the anti-Legionnaire's switch is switched off at the latest after 120<br />

minutes, even if 60 minutes at 60 °C have not yet been reached.<br />

The reference sensor for switching off this control is different in every system:<br />

• Buffer tank system: Temperature sensor Switch off auxiliary heating in the DHW standby tank<br />

• Systems with Solar and Standby Tank: Temperature sensor Collector array on / off in the solar<br />

tank<br />

• Systems with dual coil DHW supply: Temperature sensor Anti-Legionnaire's switch in the DHW<br />

standby tank<br />

Dr. <strong>Valentin</strong> Energie<strong>Software</strong> GmbH page 72 / 104