Tags and the Project Database<br />

• Dev+Limit: Limit deviation to a value higher than the DevSetpoint in a tag value that triggers an alarm.<br />

Define the alarm message in the Tag Properties dialog or on an Alarm worksheet. You can access this field<br />

during runtime.<br />

• Dev+Limit: Limit deviation to a value lower than the DevSetpoint in a tag value that triggers an alarm.<br />

Define the alarm message in the Tag Properties dialog or on an Alarm worksheet. You can access this field<br />

during runtime.<br />

• RateLimit: Limit of rate variation in a tag value that triggers an alarm. Define the alarm message in the<br />

Tag Properties dialog or on an Alarm worksheet. You can access this field during runtime.<br />

Alarms for Integer and Real Type Tags<br />

From the Tag Properties dialog, specify an alarm for integer and real-type tags as follows:<br />

• Alarms Enabled checkbox: Click (check) to enable checking according to configuration.<br />

• Remote Ack tag field: Type a tag to acknowledge this alarm.<br />

• Dead Band Value field: Type a value of the filter for alarms normalization. For example: if the TEMP1 tag<br />

is configured with an alarm with Hi Limit = 90 and Dead Band = 5, then IWS generates an alarm when<br />

TEMP1 ≥ 90. The return to normal occurs when TEMP1 ≤ 85.<br />

• Translation Enabled checkbox: Click (check) to enable the translation of messages defined on the Options tab<br />

in the Project Settings dialog. For additional information about translations, see Translation Tools.<br />

Note: IWS saves Alarm messages with the Translation Enabled attribute enabled in a file called<br />

Alarm.TXT located in your project's \DATABASE\ directory.<br />

• HiHi (HiHiLimit) checkbox: Click (check) to indicate a Very High alarm is present. Accessible during runtime.<br />

• Hi (HiLimit) checkbox: Click (check) to indicate a High alarm is present. Accessible during runtime.<br />

• Lo (LoLimit) checkbox: Click (check) to indicate a Low alarm is present. Accessible during runtime.<br />

• LoLo (LoLoLimit) checkbox: Click (check) to indicate a Very Low alarm is present. Accessible during runtime.<br />

• Rate (RateLimit) checkbox: Click (check) to indicate a Rate alarm is present. Accessible during runtime.<br />

• Deviation+ checkbox: Click (check) to indicate a Deviation alarm is present. Accessible during runtime.<br />

• Deviation- checkbox: Click (check) to indicate a Deviation alarm is present. Accessible during runtime.<br />

• Deviation SetPoint field: Specify a reference point for the deviation. Accessible during runtime.<br />

• Deviation Dead Band field: Specify a reference value for the deviation.<br />

Alarms for Boolean-Type Tags<br />

Use the Alarms-Bool Type tab on the Tag Properties dialog to specify alarm properties for Boolean-type tags.<br />

Alarms-Bool Type Tab<br />

<strong>InduSoft</strong> Web Studio Page 125