Alarms, Events, and Trends<br />

Area / Element Name<br />

Description<br />

• Keep the settings consistent, so when the user closes the screen and opens it again, or re-starts your<br />

project, the settings configured during runtime are not lost.<br />

• Create standard settings for different scenarios and load the appropriate configuration during the<br />

runtime, based on a pre-defined condition or based on the user-selection.<br />

When the tag configured in this field changes value (e.g., toggles), the current settings of the Trend object<br />

are saved in the temporary file. This command is not available for the Thin Client.<br />

Load trigger<br />

When the tag configured in this field changes value (e.g., toggles), the settings from the temporary file are<br />

loaded and applied to the Trend object during runtime.<br />

Note: After the screen where the Trend object is configured is saved, the settings are not<br />

automatically loaded from the temporary file when the screen is opened again, unless the<br />

Load trigger command is executed before the screen is closed.<br />

Custom Point<br />

Selection<br />

Export to File<br />

File Name<br />

Auto Save<br />

Screen<br />

Point Number<br />

Add Indicator<br />

Trigger<br />

File Name<br />

If this field is left blank, the temporary file is saved in your project's Web sub-folder<br />

with the syntax ScreenNameObjectIDTrendControl.stmp (e.g.,<br />

MyScreen10TrendControl.stmp). The Thin Client station saves/loads the temporary file<br />

in the standard Temp directory of the operating system (e.g., \Documents and Settings<br />

\CurrentUser\Local Settings\Temp).<br />

You can configure a customized file name for the temporary file in this field or even configure a string tag<br />

between curly brackets, so the user can change the name of the configuration file dynamically during<br />

runtime by changing the value of this tag. If you do not specify any path, the file is saved in your project's<br />

Web sub-folder by default.<br />

When this box is checked, the current settings of the Trend are automatically saved in the temporary file<br />

when the screen where the Trend is configured is closed during runtime. If the box is not checked, the<br />

settings are saved only when the Save trigger command is executed.<br />

This interface allows you to create your custom dialog to modify or insert pens to the object.<br />

Name of the screen which must be launched when the user triggers a command to modify or insert a new<br />

pen to the object during runtime.<br />

Point number (from the Points dialog), indicating the point associated to the pen that will be inserted or<br />

modified during runtime.<br />

Flag that indicates that the user triggered an action to insert a new pen (value 1) instead of modifying a pen<br />

that is already been visualized (value 0).<br />

When the tag configured in this field changes value (e.g., toggles), the current state of the trend control<br />

is exported to an image file. The toolbar and scroll bar are not included. The legend and time display are<br />

included only if the trend control is configured to show them.<br />

The file path and name of the exported file.<br />

If no path is specified, then the file is saved in the project directory. If no extension is specified, then it is<br />

determined by Format.<br />

Tip: You can specify a project tag in curly brackets (e.g., {tagname}), to<br />

programatically change the file name during runtime.<br />

Status<br />

Format<br />

Size<br />

The tag configured in this field receives status codes that indicate the success or failure of the export.<br />

The graphic format of the exported file.<br />

If Auto is selected, then the format is determined by the extension specified in File Name. If Auto is<br />

selected but no extension is specified, then the default format is BMP.<br />

The image file is exported at full size by default. However, you can specify the width and height (in pixels).<br />

Decimation Enable When this option is selected, the trends in the Trend Control object that are configured to show historical<br />

data will have their data decimated before the trends are drawn. That means for each trend, the X-axis is<br />

divided into a number of intervals (determined by Max Points) and all of the data points within each interval<br />

are averaged together to be drawn as a single point. This can improve runtime performance when there is a<br />

large amount of historical data to display, and it can make the trends easier to read.<br />

Decimation only works when the trend control is in Stop Mode (a.k.a. Historical Mode).<br />

Page 286<br />