Communication with Other Devices<br />

Tip: By default, the project will scan the communication worksheet every 600 milliseconds, which is<br />

the rate at which the system tag BlinkSlow toggles. To adjust the rate, manually edit the project file<br />

(i.e., projectname.APP) to add the following entry:<br />

[Options]<br />

MainDrvAlwaysTrigger=tagname<br />

tagname can be either another system tag (e.g., BlinkFast, Second, Minute) or a tag that you have<br />

created. Whenever the value of the tag changes, the worksheet will be scanned and the tags will be<br />

read.<br />

Standard Driver Sheets<br />

In addition to the unique MAIN DRIVER SHEET that is available for each driver, you can create several<br />

STANDARD DRIVER SHEETS for each driver. The STANDARD DRIVER SHEETS provide additional fields,<br />

which you can use to control communication.<br />

To open a STANDARD DRIVER SHEET, right-click on a driver subfolder and select Insert from the resulting<br />

popup (see the following figure).<br />

Sample STANDARD DRIVER SHEET<br />

The STANDARD DRIVER SHEET dialog is divided into two areas:<br />

• Header area (top section), contains parameters that affect the all tags configured in the Body area of this<br />

worksheet<br />

• Body area (bottom section), where you define the relationship between tags in the project and their field<br />

equipment address.<br />

Use the Header area parameters as follows:<br />

• Description field: Type a description of the STANDARD DRIVER SHEET for documentation purposes.<br />

• Increase Priority checkbox: Click (check) to keep the reading and writing commands for this sheet on the top<br />

of the communication queue whenever they are triggered.<br />

Caution: You must give special attention to this worksheet when you enable the Increase Priority<br />

option. If the worksheet keeps triggering communication commands, the project may never be<br />

able to execute the other driver sheets.<br />

• Read Trigger field: Type a tag that triggers the project to read the worksheet automatically when you change<br />

this tag's value.<br />

• Enable Read when Idle field: Type a tag or constant value. Use a tag (or constant) value greater than zero, to<br />

enable reading from the equipment.<br />

<strong>InduSoft</strong> Web Studio Page 333