Alarms, Events, and Trends<br />

UseLegacyPriorityAck=1<br />

Caution: The settings configured in the body of each Alarm worksheet are stored in the Tags<br />

Database archive(s). Therefore, changes to the tags database may affect the content of the Alarm<br />

worksheets (body). Notice that each tag/type cannot be available in more than one Alarm group<br />

simultaneously because the Alarm Group is a property associated to each Tag/Alarm Type (e.g., Tag:<br />

Level; Alarm Type: Hi; Alarm Group: 2).<br />

Alarm Worksheet Header<br />

The following table describes the Header settings on an Alarm worksheet:<br />

Field Remarks Syntax<br />

Description<br />

Group Name<br />

Email Settings<br />

Advanced<br />

On Line > Display in Alarm Controls<br />

On Line > Ack Required<br />

On Line > Beep<br />

On Line > Send to Printer<br />

Description of the alarm group. It is displayed on the workspace. This field is used for<br />

documentation only.<br />

Name of the Alarm group. During runtime, the operator can filter alarms based on the<br />

Group Name by the built-in Filters dialog of the Alarm/Event control object.<br />

Launches the Email Settings dialog, where you can configure the settings for emails<br />

sent automatically based on alarm conditions.<br />

Launches the Advanced Settings dialog, where you can configure the settings for<br />

emails sent automatically based on alarm conditions.<br />

When checked, the alarms are available to be displayed on the Alarm/Event Control<br />

object.<br />

When checked, the alarms require acknowledgment. In this case, the alarms<br />

are displayed on the Alarm/Event Control object (Online mode) until they are<br />

acknowledged AND normalized.<br />

When checked, the computer keeps beeping while there are alarm(s) to be<br />

acknowledged, currently active.<br />

When checked, the alarm messages are sent to the printer as soon as the alarm event<br />

occurs. When using this option, you must use a matrix printer (instead of DeskJet<br />

or LaserJet) in order to print the message(s) and feed just one line — otherwise,<br />

each alarm will be printed in a different sheet of paper. The alarms will be printed in<br />

the default printer. If you want to send alarms to a printer different from the default<br />

printer, you can specify the printer path/name, editing the following parameter in the<br />

project_name.APP file:<br />

Text (up to 80 chars)<br />

Text (up to 32 chars)<br />

Button<br />

Button<br />

Checkbox<br />

Checkbox<br />

Checkbox<br />

Checkbox<br />

[AlarmLog]<br />

Device=PrinterPath/PrinterName<br />

History > Save to Disk<br />

When checked, the alarm messages are stored in the history log when they become<br />

active.<br />

Checkbox<br />

Page 242<br />