Communication with Other Devices<br />

Area / Element<br />

Description<br />

Note: This is enabled by default. If it is disabled, then you must use read triggers (see<br />

below).<br />

Write actions<br />

Maximum group size<br />

Synchronous read<br />

trigger<br />

Asynchronous read<br />

trigger<br />

Read count<br />

Status<br />

Status message<br />

Maximum aging<br />

Enable write on tag<br />

change<br />

The maximum number of tag reads that may be performed in a single read operation.<br />

For example, if you have 1000 items/rows configured in the worksheet and Maximum group size is set<br />

to 100, then 10 read operations will be performed during each scan of the worksheet.<br />

When the value of this tag/expression changes, the worksheet is scanned and all tag values are read<br />

from the server. The project waits for the scan to complete before continuing.<br />

When the value of this tag/expression changes, the worksheet is scanned and all tag values are read<br />

from the server. The project continues running without waiting for the scan to complete.<br />

The name of a tag (Integer type) that will receive a count of the number of read operations performed<br />

since the project was run.<br />

The name of a tag (Integer type) that will receive a status code for the last read operation performed by<br />

a trigger.<br />

The name of a tag (String type) that will receive the corresponding status message.<br />

The maximum age (in milliseconds) of values that will be accepted from the server's cache. If a value is<br />

older than this, then the server will be forced to get the latest value from the target device.<br />

When this value is TRUE (non-zero), a write will be automatically performed whenever the value of the<br />

project tag changes.<br />

Note: This is enabled by default. If it is disabled, then you must use write triggers (see<br />

below).<br />

Reload trigger<br />

Refresh IDs on startup<br />

Maximum group size<br />

Synchronous write<br />

trigger<br />

Asynchronous write<br />

trigger<br />

Write count<br />

Status<br />

Status message<br />

The maximum number of tag writes to be performed in a single write operation.<br />

For example, if you have 1000 items/rows configured in the worksheet and Maximum group size is set<br />

to 100, then 10 write operations will be performed during each scan of the worksheet.<br />

When the value of this tag/expression changes, the worksheet is scanned and all tag values are written<br />

to the server. The project waits for the scan to complete before continuing.<br />

When the value of this tag/expression changes, the worksheet is scanned and all tag values are written<br />

to the server. The project continues running without waiting for the scan to complete.<br />

The name of a tag (Integer type) that will receive a count of the number of write operations performed<br />

since the project was run.<br />

The name of a tag (Integer type) that will receive a status code for the last write operation performed by<br />

a trigger.<br />

The name of a tag (String type) that will receive the corresponding status message.<br />

Indirect tags (e.g., {MyTag}) configured in the body of the worksheet will be reloaded only when the<br />

value of this tag/expression changes.<br />

When this option is selected, the node IDs in the worksheet will be refreshed from the specified item<br />

paths every time the project is run.<br />

Note: Refreshing IDs like this may cause the project to take longer to start up, so if you<br />

select this option, then you should also specify a root node (see below) to limit how much<br />

of the server's list of items must scanned.<br />

Enable bit notation<br />

When this option is selected, bit notation is allowed in the Item column of the worksheet body.<br />

Note: IWS's OPC client does not normally use the Triggering Mode that is defined the OPC<br />

protocol. Instead, it allows any change in any tag/expression to be used as a trigger. If you want<br />

to use Triggering Mode, configure one worksheet to read the trigger values and then configure<br />

another worksheet that specifies the read values as triggers.<br />

5. Click OK to close the Advanced dialog and return to the worksheet.<br />