Alarms, Events, and Trends<br />

Type<br />

Date/Time<br />

Description<br />

Displays the value in the Date/Time format (e.g., MM/DD/YYYY HH:MM:SS). This setting is available only when the Data<br />

Source type is set to Database.<br />

Note:<br />

• When the Data Source type is set to Database, it is important to make sure that the Type for each<br />

column configured in the object matches the Type of the respective field in the database.<br />

• When the Data Source type is set to Database, you can configure valid SQL statements<br />

directly in the field (e.g., List(DISTINCT [Cell_Name]) AS [Cell Name]). You can also<br />

configure tag names between curly brackets to modify this setting during runtime (e.g.,<br />

{MyFieldName}).<br />

Tip: If Picture is the column type, the Grid object displays a default icon ( ) if the picture file is<br />

not found during runtime. You can configure a different picture to be displayed when the file is<br />

not found by copying the picture file to the Web sub-folder of your project folder and configuring<br />

its name on the project_name.app file, as follows:<br />

[Objects]<br />

GridDefaultPicture=PictureFileName<br />

• Width: Enter a width of the column, in pixels.<br />

• Align: Select an Alignment for the data shown in the column. There are three options: Left, Right or Center.<br />

• Input: Click (check) to allow the user to enter data in this column during runtime.<br />

• Key: Use this field to designate a shortcut for sorting the values. A shortcut is a combination of keys<br />

pressed on a keyboard at one time (e.g., CTRL+C, CTRL+V, etc.). This option is especially useful when<br />

creating projects for runtime devices that do not provide a mouse or touchscreen interface and only have a<br />

keyboard for interacting with the project during runtime.<br />

• Unit: Enter the name of the engineering unit (i.e., the unit of measurement), if any, that applies to the data<br />

displayed. You can also enter a String tag using the {tagname} syntax, which allows you to change the<br />

value of Unit during runtime.<br />

• Decimal Points: Enter the number of decimal places to be displayed. You can also enter an Integer tag using<br />

the {tagname} syntax, which allows you to change the value of Decimal Points during runtime.<br />

Note: When the Data Source type is set to Class Tag, and the Columns dialog is left blank, the<br />

object displays the values from all members of the Class tag with the following default column<br />

settings:<br />

• Label = <br />

• Type = Text<br />

• Width = <br />

• Align = Center<br />

• Input = Enabled (checked)<br />

• Key = <br />

• Unit = <br />

The Unit of a class member or tag is set using the Tag Properties tool.<br />

• Show ID Column: Check to display the number of each row, automatically.<br />

• Allow sorting columns: Check to enable the user to sort the values in the columns during runtime, either by<br />

clicking on the label or by using the shortcut configured for each column. This option is disabled if the<br />

Show header option from the Advanced dialog is not checked.<br />