Communication with Other Devices<br />

The MAIN DRIVER SHEET dialog displays (see the following figure).<br />

Sample MAIN DRIVER SHEET<br />

The MAIN DRIVER SHEET worksheet is divided into two areas:<br />

• Header area (top section), contains parameters that affect the all tags configured in the Body area of this<br />

worksheet; and<br />

• Body area (bottom section), where you define the relationship between tags in the project and their field<br />

equipment address.<br />

Use the Header area parameters as follows:<br />

• Description field: Type a description of the MAIN DRIVER SHEET for documentation purposes.<br />

• Disable field: Type a tag or an expression to enable and disable the communication of each MAIN DRIVER<br />

SHEET on the fly.<br />

• Type a value (or expression result) that is greater than zero to disable the MAIN DRIVER SHEET.<br />

• Type a zero (or leave this field blank) to enable the MAIN DRIVER SHEET.<br />

• Read Completed field: Type in a tag and the communication driver toggles the tag when it completes a read<br />

command.<br />

• Read Status field: Type in a tag, which is updated with the status of the last read command.<br />

• Write Completed field: Type in a tag and the communication driver toggles the tag when it completes a write<br />

command.<br />

• Write Status field: Type in a tag, which is updated with the status of the last write command.<br />

• Min and Max checkbox: Click (check) to specify minimum and maximum values for data from the field<br />

equipment.<br />

• Min and Max fields (become active only when you enable the Min and Max checkbox): Type a range of values,<br />

which can be converted into an engineering format.<br />

The project uses these fields to determine a minimum/maximum range of values for data from the field<br />

equipment. The scaling is done automatically. You must configure the engineering range using the Min and<br />

Max parameters on the Tag Properties dialog. This range affects all tags in the worksheet, except those with<br />

customized Min and Max values, as specified in the Body area of the driver sheet (Min and Max columns).<br />

Use the Body area parameters as follows:<br />

• Tag Name field: Type the name of a project tag to be used by the communication driver.<br />

• Station field: Type the number of the equipment station within the network. The syntax in this field varies<br />

with each communication driver. Refer to the appropriate driver's documentation for further information.<br />

Tip: For some drivers, if you've configured the driver to do serial encapsulation via TCP/IP or<br />

UDP/IP, then the station may be specified using the following format:<br />

IP_address:port_number|station<br />

<strong>InduSoft</strong> Web Studio Page 331