About thin clients and mobile access<br />

Term<br />

IP_ROUTER_LAN<br />

IP_ ROUTER_WAN<br />

ScreenName<br />

Description<br />

IP Address of the Router on the LAN.<br />

IP Address of the Router on the WAN.<br />

Name of the project screen, saved as HTML, that is open on the Thin Client station.<br />

Example 1: Web Server and Thin Client in the same Intranet (LAN)<br />

This is the very common architecture, as well as the simplest to configure. In this architecture, both the Web<br />

Server (e.g., Microsoft IIS) and the Data Server (i.e., the IWS TCP/IP Server module) are running on the same<br />

PC. The Thin Client connects to the Web Server to download the HTML screen file(s). Then it connects to<br />

the Data Server to exchange data with the IWS runtime project. Since both the Thin Client and the Server<br />

station are connected to the same network, the Thin Client can access the Server station directly through its<br />

IP address (or host name).<br />

Configuration:<br />

Setting WTG Enabled Web Gateway Disabled<br />

Data Server IP Address IP_SERVER_LAN IP_SERVER_LAN<br />

Secondary Data Server IP Address - -<br />

Web Tunneling Gateway IP Address IP_SERVER_LAN -<br />

Web Tunneling Gateway Secondary IP Address - -<br />

Note:<br />

• URL From Thin Client LAN: http://IP_SERVER_LAN/ScreenName.html<br />

• Home directory of the web server (HTTP server) on the server station: Web sub-folder of the project<br />

Example 2: Web Server with Intranet (LAN) and Internet (WAN) Connections<br />

This architecture has both the Web Server (e.g., Microsoft IIS) and the Data Server (i.e., the IWS TCP/IP<br />

Server module) running on the same PC. Thin Clients can connect to the Server through either an Intranet<br />

(LAN) connection to the Server or an Internet (WAN) connection to the Server (e.g., two different Ethernet<br />

ports).<br />

Configuration:<br />

<strong>InduSoft</strong> Web Studio Page 445