Alarms, Events, and Trends<br />

• Print Trigger: When the tag configured in this field is toggled, the current state of the Alarm/Event Control<br />

object is sent to the default printer.<br />

• PDF Trigger field: When the tag configured in this field is toggled, the current state of the Alarm/Event<br />

Control object is saved as a PDF file at the location specified by PDF Filename.<br />

• PDF Filename field: Enter a complete file path and name where the PDF file is to be saved. You can also enter<br />

a tag name using the {tag} syntax.<br />

Note: PDF Trigger and PDF Filename are not supported in projects running on Windows Embedded or<br />

Thin Client.<br />

• Multiline checkbox: When this option is checked, the print output or PDF will be formatted according to the<br />

available column space, and the text within each cell will be wrapped so that all of it is shown.<br />

• Total items field: Type an integer tag to see how many alarms remain after IWS filters the alarm object using<br />

parameters specified on the Filters dialog.<br />

• Auto Format checkbox: When checked, decimal values in the Display Value, Previous and Value columns will<br />

be formatted according to the virtual table created by the SetDecimalPoints() function.<br />

• Selected tag field: Type a string tag to enable the end user to click on an alarm message to see the name of<br />

the tag associated with that alarm event.<br />

• First Row Text field: Type a string tag. This tag will receive the text of all fields from the first row of the Alarm/<br />

Event Control. The fields are tab delimited. Whenever the first row changes — either due to a new Alarm/<br />

Event, or simply because the rows are reordered — the value of the configured tag is updated.<br />

• Summary Changes field: Type an integer tag. This tag will receive a running count of the number of changes in<br />

the Alarm/Event Control. For example, when a new Alarm occurs or when an Alarm is acknowledged, the<br />

value of the configured tag will be incremented. Reordering the rows is not counted as a change.<br />

• Click the Navigation Triggers button to open the following dialog:<br />

Navigation Triggers dialog<br />

You can make the on-screen Alarm Control object scroll up, scroll down, page up, page down, go to home<br />

(beginning) of page, or go to end of page by configuring tags in the corresponding fields. Whenever the<br />

values of the configred tags change, the Alarm Control object will navigate that way. This is useful for<br />

adding navigation controls to the screen; for example, if you configure the same tag to the Up field in this<br />

dialog and a Pushbutton object, then the Alarm Control object will scroll up whenever the Pushbutton<br />

object is pressed.<br />

When you are finished, click OK to close the Advanced dialog.<br />

Fonts<br />

Click the Fonts button to open a standard Fonts interface where you can specify display properties for the<br />

message text.<br />

Format<br />

Use the Format area of the object properties to configure the appearance of the Alarm/Event Control object<br />

during run time:<br />

Page 260<br />